ENS 40393
ENS Event | |
---|---|
05:00 Oct 16, 2003 | |
Title | 10 Cfr 21.21 Potential Failure of Solenoid Operated Valve to Close at Elevated Air Pressure |
Event Description | The following is taken from a facsimile from Automatic Valve:
Describe Problem (Initial Concern and Symptoms): On 10/16/2003 Paul Chenell of Dresden reported that a B7122-145, serial number 64065 shipped on 12/11/2002, valve failed to exhaust air with both solenoids de-energized causing the CRD valve to remain in the open position. On 10/17/2003 the valve was delivered to Automatic Valve for analysis of the problem. Contain Symptom (Action): Re-inspect all existing 6910-001 plungers to verify the correct overall length (Done 10-17-03). Rebuild, retest, and return the B7122-145 valves to Dresden (Shipped 11-26-03). Notify customers potentially impacted, by Fax, to inspect plunger lengths (10/24/03). Inspect all units installed at Dresden station (completed 10-30-03, 15 of 274 plungers found out of specification) Inspect all units installed at Cooper station (completed 10-29-03, 0 of 64 plungers found out of specification) Hold shipment for all 6910-001 plungers from suspect lot. Root Cause/s of Problem: 10 CFR Part 21 Report Required: Yes The valve was first functionally tested in the normal manner- that is at 35 psig low pressure & at 145 psig high pressure. The valve functioned without problems at low pressure but failed to return to its normally closed position at 145 psig when both solenoids were de-energized. Further functional testing revealed that at an inlet pressure of approximately 100 psig the valve would fail to return when de-energized. When the valve was disassembled, the plunger in the number 2 solenoid, the left hand solenoid when facing the exhaust port, was found to be approximately .020 too long - 1.315" compared to the specified length of 1.290 +.005/-.003. Because the plunger only has a total stroke of less than .030, the natural expansion of the seal material in the plunger, due to a combination of heat and pressure, combined with the out of specification length created a situation where the plunger had no room to move and thus exhaust pilot air when the solenoid was deenergized. The root cause of the failure is the out of spec plunger. Procedures require the lengths of all plungers to be inspected prior to use. Analysis of the results of measurement testing revealed an unexpected degree of variation In recorded lengths. Variation was traced to the use of different types of equipment and the inherent difficulty in measuring compressible material with pressure sensitive measurement devices. This may have lead to some units being categorized as In specification initially and out of specification at subsequent inspection. (Refer to corrective action 5.1). Notwithstanding measurement variation, the primary root cause of the observed plunger dimensions is changes to the length of the fluorocarbon insert after it is pressed into the plunger body. This variation is detectable and beyond measurement uncertainty. Dissection of returned plungers revealed abnormal compression set among all plungers which were beyond specification limits and normal compression set among plungers which were within specification limits. Chemical analysis and durometer testing did not show any significant differences In the chemical properties or material hardness of the lot or in previous lots of identical insert material. However, the following results were obtained when plunger insert samples were compressed by 23 for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at 230 degrees F: Scenario [Average Set %, # tested] Unused insert, suspect lot, visible set, as received [92%, 3] Unused insert, suspect lot, visible set, post cured at 260 F [11%, 2] Unused insert, previous lot no visible set, as received [10%, 3] Unused insert, suspect lot no visible set, as received [9%,, 2] Field return Insert, suspect lot, visible set [36%, 4] Field return Insert, suspect lot, no visible set [10%, 2] From this we concluded that there is a cure problem with a portion of the suspect lot and that post cure takes place when the solenoid is continuously energized. Based on the test results, we believe that a portion of the lot was not properly post cured. The degree of growth of the plunger insert due to compression set is observed to be variable. This depends on exact dimensions of the molded insert when installed, the ID of the plunger retaining the insert and the exact cure duration variation of the bad plunger inserts. The degree of growth also seems to be terminal. Returned plungers (field failure) and other samples from the suspect lot on hand) at Automatic Valve have not changed dimensions during the period of study. Five plungers tested at 200 degrees F for five days exhibited thermal expansion and did not detectably change size when cooled down. Ten plungers subjected to 230 degrees F for ten days exhibited thermal expansion and did not detectably change size when cooled down. (Refer to corrective action 5.2, 5.3) 5. Corrective Action: 5.1) Specific individual measurement equipment is specified for plunger measurement. 5.2) Specific lot definition based on curing process (as opposed to pre-vulcanized rubber lot) to define lot homogeneity for all plunger inserts 5.3) A sample of each homogeneous processed sample to be tested for compression set as part of dedication process. Test Conducted to Verify It: Test samples to be placed under worst case temperature and pressure characteristics for a period of 10 months. 6. Implementation (Describe: Include Applicable CN Numbers): CN 8897 defines lot and compression set and measurement characteristics for 6910-001 plungers.. 7. Corrective Action to System to Prevent Recurrence: To be determined. The following plants have components containing the suspected lots as follows: Nebraska Public Power - Cooper Station Exelon - Limerick, Peach Bottom, Quad Cities, Dresden |
Where | |
---|---|
Automatic Valve Novi, Michigan (NRC Region 3) | |
Organization: | Automatic Valve |
Reporting | |
10 CFR 21.21 | |
Time - Person (Reporting Time:+1473.02 h61.376 days <br />8.768 weeks <br />2.018 months <br />) | |
Opened: | Todd Hutchins (Email) 15:01 Dec 16, 2003 |
NRC Officer: | Gerry Waig |
Last Updated: | Dec 16, 2003 |
40393 - NRC Website | |
Automatic Valve with 10 CFR 21.21 | |
WEEKMONTHYEARENS 466922011-03-22T04:00:00022 March 2011 04:00:00
[Table view]10 CFR 21.21 Valve Plunger Guide Malfunction ENS 403932003-10-16T05:00:00016 October 2003 05:00:00 10 CFR 21.21 10 Cfr 21.21 Potential Failure of Solenoid Operated Valve to Close at Elevated Air Pressure 2011-03-22T04:00:00 | |