ENS 40168
ENS Event | |
|---|---|
13:00 Sep 18, 2003 | |
| Title | Unusual Event Declared Due to Expected Severe Weather |
| Event Description | At 0900 EDT the licensee declared an Unusual Event as a precautionary measure due to expected severe weather from hurricane Isabel. Current wind speed and direction is 10-15 mph sustained with gusting to 20 mph from the NNE direction. No additional staff other than those for the planned outage have been brought onsite.
The licensee informed state/local agencies and the NRC Resident Inspector.
As of 1600 ET, Surry Unit 1 commenced a power reduction of 200 mwe (100% to approximately 75% power) in anticipation of grid instabilities due to heavy weather. One of eight circ water screens is degraded due to river debris and its associated circulating water pump has been secured. On-site meteorological panels are out of service. Additionally, the Emergency Operating Facility (EOF) is out of service due to a loss of power. Notified R2DO (A. Boland).
The following was received via fax from the licensee: With Surry Power Station Unit 1 at approximately 75% reactor power and Unit 2 at 100% reactor power, a manual reactor trip was initiated on Unit 1 at 1728 and on Unit 2 at 1732, due to the loss of the '1G' and `2G' buses which supply power to all eight circulating water pumps for both units. The loss of the buses occurred during high winds and rain associated with Hurricane Isabel, although no hurricane force winds were onsite prior to or at the time of the event. A discretionary Notification of Unusual Event had been declared earlier at 0900 due to the severe weather. On Unit 1, the 'B' inadequate core cooling monitor (ICCM) failed. The 'A' ICCM remained operable throughout. All control rods fully inserted and the shutdown margin for Unit 1 was determined to be satisfactory. On Unit 2, eight rod position indicators showed greater than 10 steps but less than 20 steps following the reactor trip. Emergency boration was initiated. All Unit 2 IRPIs [Individual Rod Position Indications] are currently indicating less than five steps and the shutdown margin was satisfactory. Auxiliary feedwater automatically initiated as designed for both units on low low steam generator level following the trip. Primary RCS temperature decreased to approximately 543 and 538 degrees on Unit 1 and 2 respectively and was stabilized at 547 degrees. No primary safety or relief valves were actuated during the event on either unit. As a result of the loss of the circulating water pumps, the emergency service water pumps were started to conserve intake canal level. After start, 2 out of the 3 emergency service water pumps tripped on high water temperature. The pumps were checked and restarted 14 minutes later. Also due to the need to conserve intake canal level, the main steam trip valves on both units were closed and primary temperature is being maintained by use of the secondary power operated relief valves. No indication of primary to secondary leakage exists on either unit, therefore no adverse radiological consequences resulted from this event. Both units are currently stable at hot shutdown. At 1845, the 2G bus was energized and circulating water pumps were started. The emergency service water pumps were secured and are in standby. This 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> report is being made for Surry Units 1 and 2 in accordance with 10 CFR 50.72(b)(2)(iv)(B) and 10 CFR 50.72(b)(3)(iv)(A). Notified R2DO (A. Boland), NRR EO (J. Calvo), DIRO (R. Wessman), FEMA (Chuck Bagwell), DHS (Colleen Wilson).
The licensee terminated their unusual event due to the following conditions: - severe weather has left the area - both units are stable at hot shutdown on offsite power - 2 of 3 ESW pumps are operable, and the third ESW pump is being prepared for an operational test - 45 of 67 sirens remain inoperable, but the sirens will be restored when power to the grid is restored The licensee will notify the NRC Senior Resident Inspector, as well as state and local officials Notified R2DO (Boland), NRR EO (Calvo), DIRO (McGinty), FEMA (M. Eaches), DHS (D. Licastro) |
| Where | |
|---|---|
| Surry Virginia (NRC Region 2) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| Time - Person (Reporting Time:+-3.73 h-0.155 days <br />-0.0222 weeks <br />-0.00511 months <br />) | |
| Opened: | Terry Huff 09:16 Sep 18, 2003 |
| NRC Officer: | Steve Sandin |
| Last Updated: | Sep 18, 2003 |
| 40168 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | Yes, Manual Scram |
| Before | Power Operation (75 %) |
| After | Hot Shutdown (0 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | Yes, Manual Scram |
| Before | Power Operation (100 %) |
| After | Hot Shutdown (0 %) |
Surry | |
WEEKMONTHYEARENS 580202025-11-03T17:15:0003 November 2025 17:15:00
[Table view]10 CFR 50.72(b)(3)(iv)(A), System Actuation Emergency Diesel Generator (EDG) Actuation ENS 578542025-08-06T22:47:0006 August 2025 22:47:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 571582024-06-02T21:08:0002 June 2024 21:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip ENS 537362018-11-12T05:00:00012 November 2018 05:00:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuation ENS 536622018-10-11T04:00:00011 October 2018 04:00:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Actuation of Emergency Diesel Generator Due to Transformer Trip ENS 531702018-01-17T14:52:00017 January 2018 14:52:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Auto-Start of Emergency Diesel Generator Due to Transformer Fuses Being Disconnected ENS 522922016-10-09T06:54:0009 October 2016 06:54:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Following Main Generator Differential Lockout Turbine Trip ENS 514672015-10-13T22:15:00013 October 2015 22:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip After a Turbine Trip ENS 514022015-09-17T00:14:00017 September 2015 00:14:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Start and Loading of the #2 Emergency Diesel Generator ENS 512442015-07-21T09:04:00021 July 2015 09:04:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Surry Unit 2 Trip During Reactor Startup ENS 505292014-10-13T11:58:00013 October 2014 11:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to a Spurious Overpower / Delta Temperature Signal ENS 486382012-12-29T13:03:00029 December 2012 13:03:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Emergency Diesel Generator Auto-Start and Load Upon Trip of Reserve Station Transformer ENS 471892011-08-23T18:04:00023 August 2011 18:04:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of an Unusual Event Due to a Seismic Event ENS 469052011-05-30T12:08:00030 May 2011 12:08:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuation - Afw Initiation ENS 467612011-04-16T22:55:00016 April 2011 22:55:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Loss of All Offsite Power from Tornado Damage ENS 465842011-02-02T10:33:0002 February 2011 10:33:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Loss of Rcs Coolant Flow in One Loop ENS 459862010-06-08T13:48:0008 June 2010 13:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Automatic Reactor Trip with Safety Injection Due to Loss of Vital Ac Bus ENS 455282009-11-29T15:45:00029 November 2009 15:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Trip from Intermediate Range Due to Rod Group Demand Counter Discrepancy ENS 442212008-05-17T13:04:00017 May 2008 13:04:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Failed Relay Causes Emergency Diesel Generator to Start ENS 441522008-04-21T02:16:00021 April 2008 02:16:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 1 Manual Reactor Trip Due to Main Turbine Vibrations ENS 428882006-10-07T22:01:0007 October 2006 22:01:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Manual Scram Due to Unusual Noise in Turbine Building ENS 413832005-02-08T01:23:0008 February 2005 01:23:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip During Startup Due to Indication of Misaligned Rod ENS 411762004-11-06T07:52:0006 November 2004 07:52:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Due to a Fire in the Unit 1 Turbine Basement ENS 407682004-05-22T01:16:00022 May 2004 01:16:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared ENS 407692004-05-22T01:08:00022 May 2004 01:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Generator Leads Failure ENS 401682003-09-18T13:00:00018 September 2003 13:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Expected Severe Weather 2025-08-06T22:47:00 | |