BSEP 03-0066, Notification of Emergency Response Data System Modification
| ML031200542 | |
| Person / Time | |
|---|---|
| Site: | Brunswick |
| Issue date: | 04/23/2003 |
| From: | O'Neil E Carolina Power & Light Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| BSEP 03-0066 | |
| Download: ML031200542 (7) | |
Text
C' CP&L APal p
Emny Conpan APR 2 3 2003 SERIAL: BSEP 03-0066 10 CFR 50, Appendix E rA.. Nuclear Regulatory Commission ATIN: Document Control Desk Washington, DC 20555-0001 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. 1 AND 2 DOCKET NOS. 50-325 AND 50-324/LICENSE NOS. DPR-71 AND DPR-62 NOTIFICATION OF EMERGENCY RESPONSE DATA SYSTEM MODIFICATION Ladies and Gentlemen:
On June 9, 1992 (Serial: NLS-92-140), Progress Energy Carolinas Inc. (PEC) submitted the Emergency Response Data System (ERDS) Data Point Library for the Brunswick Steam Electric Plant, Units 1 and 2. In accordance with 10 CFR 50, Appendix E, Section VI.3.a, this letter provides notification of a change to a transmitted data points in the Unit 1 and Unit 2 ERDS Data Point Libraries.
As a result of installation of a new digital Power Range Neutron Monitoring (PRNM) system on Unit 2, the number of Average Power Range Monitor (APRM) inputs to data point C51CO010, "NI POWER RNG," was changed from six to four. This change was implemented on March 30, 2003.
Also, on March 30, 2003, PEC implemented extended power uprate on Unit 2. As a result, the "Engr Units Conversion" field for data point C51C0010, has been revised to reflect the uprated thermal power level.
PEC also upgraded the feedwater control system. As a result of this modification, maximum instrument range for data point C51C8003, "MAIN FD FLOW," was changed from 0.120E+02 to 0.160E+02 and a note was added to indicate that this is the actual field instrument range. This modification was completed on March 29, 2003. A similar change to the instrument range for Unit 1 data point C51C8003 was made in March 2002.
The enclosure to this letter provides revised Data Point library Reference File sheets for Unit 1 data point C51C8003, and Unit 2 data points C51C0010 and C51C8003.
Brunswick Nuclear Plant P.O.
Box 10429 Southport, NC 28461 At 2
Document Control Desk BSEP 03-0066 / Page 2 Please refer any questions regarding this submittal to Mr. Leonard R. Beller, Supervisor -
Licensing/Regulatory Programs, at (910) 457-2073.
Sincerely, Edward T. ONeil Manager - Support Services Brunswick Steam Electric Plant MAT/mat
Enclosure:
Revised Data Point Library File Sheet - Unit 1 - Data Point CS 1C8003 Revised Data Point Library File Sheet - Unit 2 - Data Point C5 C0010 Revised Data Point Library File Sheet - Unit 2 - Data Point C51C8003
Document Control Desk BSEP 03-0066 / Page 3 cc:
U. S. Nuclear Regulatory Commission, Region II ATTN: Mr. Luis A. Reyes, Regional Administrator Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, GA 30303-8931 U. S. Nuclear Regulatory Commission AT1'N: NRC Resident Inspector 8470 River Road Southport, NC 28461-8869 U. S. Nuclear Regulatory Commission (Electronic Copy Only)
ATTN: Ms. Brenda L. Mozafari (Mail Stop OWFN 8G9) 11555 Rockville Pike Rockville, MD 20852-2738 Ms. Jo A. Sanford Chair - North Carolina Utilities Commission P.O. Box 29510 Raleigh, NC 27626-05 10
BSEP 03-0066 Enclosure REVISED DATA POINT LIBRARY FILE SHEETS UNIT 1 - C51C8003 UNIT 2 - C51CO010 & C51C8003
Page 17 DATA POINT LIBRARY REFERENCE FILE Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Locations:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation For DP Transmitters:
Level Reference Leg:
Unique System Desc.:
03/28/02 BK1 N/A MAIN FD FLOW C51C8003 TOTAL FEEDWATER FLOW SMOOTHED Feedwater Flow into the Reactor System A
MLBHR Square root (feedwater flow) 0.00E+00
- 0. 160E+02 (actual field instrument range)
N/A N/A P
2 {feedwater flow inputs)
Sum smoothed, density compensate flows FE @ #5 FW heater outlet; FT @ TB 20' el N/A N/A N/A N/A, need 2 2 inputs for GOOD y
N/A Processing includes smoothing with a 30 Second time constant and compensation for Feedwater temperature and reactor pressure.
Feed flow input points default to actual Values when inputs exceed signal ranges.
I
Page 61 DATA POINT LIBRARY REFERENCE FILE Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Locations:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation For DP Transmitters:
Level Reference Leg:
Unique System Desc.:
03/30/03 BK2 N/A NI POWER RNG C51CO010 RX VALIDATED POWER - - READOUT Niicleair Tnstruments. Pnwer Range A
Linear (APRM reading); 1% = 29.23 MWt 0.00E+00 0.125E+03 N/A N/A P
4 (APRM inputs)
APRM Weighted average
- Gain Adj Factor APRM signals to Control Room meters NIA NIA NIA N/A, need > 2 inputs for GOOD N/A N/A Gain Adj Factor is processed from various heat-balance related sensors. APRM input points default to actual values when inputs exceed signal ranges.
I I
Page 68 DATA POINT LIBRARY REFERENCE FILE Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Spec Point Desc.:
Generic/Cond Desc.:
Analog/Digital:
Engr Units/Dig States:
Engr Units Conversion:
Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Locations:
Alarm/Trip Set Points:
NI Detector Power Supply Cut-off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation For DP Transmitters:
Level Reference Leg:
Unique System Desc.:
03/29/03 BK2 N/A MAIN FD FLOW C51C8003 TOTAL FEEDWATER FLOW SMOOTHED Feedwater Flow into the Reactor System A
MLB/HR Square root (feedwater flow) 0.00E+00 0.160E+02 (actual field instrument range)
N/A N/A P
2 1 feedwater flow inputs)
Sum smoothed, density compensate flows FE @ #5 FW heater outlet; FT @ TB 20' el LOW = 0.300E+I N/A N/A N/A, need 2 2 inputs for GOOD y
N/A Processing includes smoothing with a 30 Second time constant and compensation for Feedwater temperature and reactor pressure.
Feed flow input points default to actual Values when inputs exceed signal ranges.
I