3F0303-06, Revision to National Pollutant Discharge Elimination System (NPDES) Permit

From kanterella
Jump to navigation Jump to search
Revision to National Pollutant Discharge Elimination System (NPDES) Permit
ML030760019
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 03/06/2003
From: Franke J
Progress Energy Florida
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
3F0303-06
Download: ML030760019 (8)


Text

tj Progress Energy Crystal River Nuclear Plant Docket No 50-302 Operating license No DPR-72 Ref: ITS Appendix B March 6, 2003 3F0303-06 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001

Subject:

Crystal River Unit 3 - Revision to National Pollutant Discharge Elimination System (NPDES) Permit

References:

1. Minor Permit Revision - Reduction of Analysis Frequency for Oil and Grease and Total Dissolved Solids at EFF7-B - Florida Power Industrial Wastewater Permit FL0000159 dated March 21, 2002
2. Response to Request for Additional Information to Minor Permit Revision - Reduction of Analysis Frequency for Oil and Grease and Total Dissolved Solids at EFF7-B - Florida Power Industrial Wastewater Permit FLOO00159 dated June 21, 2002
3. Permit Revision (Minor) - Wastewater Permit FL0000159 - Florida Power-Crystal River Power Plant Units 1, 2 and 3 - Wastewater Permit FL0000159 dated January 29, 2003

Dear Sir:

In accordance with the Environmental Protection Plan (Non-Radiological) Technical Specifications for Crystal River Unit 3 (CR-3), Section 3.2.3, Progress Energy Florida, Inc. hereby provides notification of a change to the National Pollutant Discharge Elimination System (NPDES) Permit recently approved for CR-1/2 and CR-3 by the State of Florida, Department of Environmental Protection (FDEP).

In Reference 1, Florida Power Corporation, now doing business as Progress Energy Florida, Inc., submitted an application to FDEP requesting a minor revision of Wastewater Permit FL0000159 for reduction of the monitoring frequency for oil and grease and total suspended solids at sampling point EFF-7B. The response to a request for additional information was provided to FDEP by letter dated June 21, 2002 (Reference 2). By letter dated January 29, 2003 (Reference 3), which was postmarked and received on February 25, 2003 and February 28, 2003, respectively, Progress Energy Florida, Inc. received the FDEP approval to the requested minor permit revision (Attachment).

Progress Energy Florida, Inc Crystal River Nuclear Plant 15760 W Powerline Street Crystal River. FL34428 (11Qc I

U. S. Nuclear Regulatory Commission Page 2 of 2 3F0303-06 If you have any questions regarding this submittal, please contact Mr. Michael Shrader at (727) 826-4050 or Mr. Pete Ezzell at (352) 563-4778.

Sincerely, J. A. Franke Plant General Manager JAF/PFE/ff Attachment xc: NRR Project Manager Regional Administrator, Region II Senior Resident Inspector Allen Hubbard

PROGRESS ENERGY FLORIDA, INC.

CRYSTAL RIVER UNIT 3 DOCKET NUMBER 50-302 / LICENSE NUMBER DPR-72 ATTACHMENT PERMIT REVISION (MINOR)

Wastewater Permit FL0000159 Florida Power-Crystal River Power Plant Units 1, 2 and 3 Wastewater Permit FL0000159

4 Department of SFLORI \ Environmental Protection Twin Towers Office Building Jeb Bush 2600 Blair Stone Road David B.Struhs Governor Tallahassee, Florida 32399-2400 Secretary January 29, 2003 Mr. Daniel L. Roderick Director Site Operations Crystal River Nuclear Plant 15760 W. Powerline Street Crystal River, Florida 34428 RE: Permit Revision (Minor)

Wastewater Permit FLOOO 159 Florida Power -Crystal River Power Plant Units 1, 2 and 3 Wastewater Permit FL0000159

Dear Mr. Roderick:

The Department received your application on June 25, 2002 requesting a minor revision of Wastewater Permit FL0000159 for reduction of the monitoring frequency for oil and grease and total suspended solids at sampling point EFF-7B, discharged to waters of state via Outfall D-OF.

The monitoring frequency for oil and grease and total suspended solids will be reduced from 1/Day during discharge to 1/Week during discharge. The Department hereby approves the request pursuant to Rules62-620.200(24) and (25), and 62-620.325, F.A.C. A draft minor permit revision was issued on September 9, 2002 and a notice of intent to issue a minor permit revision was issued on November 25, 2002.

Attach this letter to Wastewater Permit FL0000159 and insert the revised pages and DMR (enclosed) into the Permit. All conditions of the Permit shall remain in effect except as revised herein. Any party to this order (permit) has the right to seek judicial review of the permit under section 120.68 of the Florida Statutes, by the filing of a Notice of Appeal under Rule 9.110 of the Florida Rules of Appellate Procedure, with the Clerk of the Department of Environmental Protection, Office of General Counsel, Mail Station 35, 3900 Commonwealth Boulevard, Tallahassee, Florida 32399-3000 and by filing a copy of the notice of appeal accompanied by the applicable filing fees with the appropriate district court of appeal. The notice of appeal must be filed within thirty days after this notice is filed with the Clerk of the Department.

"More Protection, Less Process" Pnnted on recycled paper

Wastewater permit revision (minor) Page 2 of 2 Florida Power - Crystal River Units 1, 2 and 3 Wastewater permit FL0000159 If you have any questions about this permit revision, please contact Allen Hubbard in the Industrial Wastewater Section at (850) 245-8592.

Sincerely, Mimi Drew Director Division of Water Resource Management Copies furnished to:

Yanisa Angulo- DEP Tampa

PERMITTEE: PERMIT NUMBER: FLO000159REV.*A Florida Power ISSUANCE DATE: January 8, 1999 Crystal River Power Plant EXPIRATION DATE: January 7, 2004 Unit 1, 2, & 3 APPLICATION NO.: FL0000159-001-IWIS Post Office Box 14042 St. Petersburg, Florida 33733 Page 6 of 36

  • Changes are denoted as underline.
4. During the period beginning on the effective date of this permit and lasting through expiration, the permittee is authorized to discharge from outfall D-OF [formerly (OSN) 0061 - Nuclear Services and Decay Heat Seawater System effluent [includes outfall I-FE (formerly 003) - Laundry and Shower Sump Tank (LSST) and I-FG (formerly OSN 007) - SDT-1, effluent from the Evaporator Condensate Storage Tank (ECST), and effluent from the Condensate System (CD)] to the site discharge canal thence the Gulf of Mexico.
a. Such discharges shall be limited and monitored by the permittee as specified below:

"-DISCHARGE -- -MONJTORING.

LIMITAIONS I _

TOOURIMNG~~

EFFLUENT Daily Daily Measurement Sample Sample CHARACTERISTIC Maximum Average Frequency Type Point

-Intake F1ow,'MGD, -,Report  :,-,Report-,-,, Hourly>- ,->'-- -Pump Logi, .INT-7A:

Oil and Grease, mg/i (CD and ECST) 20 15 1/Week Grab EFF-7B Oil and Grease; mg/l (D-0F) - 5.0t , > -- " /Diy_6f'Discharge Grab *,> IEFF-7 ECST Flow, MGD Report Report I/Day of Discharge Recorded EFF-7B Calculation CD Systeri Flow, MGD Reort Relidrt>":1/Day of Discharge'-: ecbrded. EFF-7B K- - - -  ;- Ca ciilation Total Suspended Solids, mg/i (CD and ECST) 100.0 30.0 I/Week Grab EFF-7B Total Suspeiinded Solids, mg/l (D-0F) 100.02*. :_*. 30.0 *iz,-,;;-5,1/DayofDischarge, Grab -. -EFF-7,:.

Total Recoverable Copper, xg/l 2.93 Report I/Day of Discharge Grab EFF-7

-Total Re6overable Iron, xg/f1 ---- ,! -ý 300.0 -- Report 4-/Day of Discharge - Grab EFF7, Total Iron, lbs/MG of Metal Cleaning Waste Report 3 8.3454 l/Day of Discharge Grab EFF-7B (MCW) generated 3

Total Copper, lbs/MG of Metal Cleaning Waste Repor O 8.345 1_/Day of Discharge Grab- EEFF-7B (MCW) generated - '- '* -.- " - -

Monitoring requirements are only applicable if the discharge from I-FE and I-FG (formerly OSNs 003 and 007), the CD discharge or the ECST (following adequate mixing) exceeds the daily maximum limitation of 20 0 mg/I or a minimal dilution rate of 4 to I is not achieved 2 Monitoring requirements only applicable if the discharge from I-FE and I-FG, the CD discharge or the ECST (following adequate mixing) exceeds the daily maximum limitation of 100 0 mg/l or a minimal dilution rate of 4 to I is not achieved 3 Limitations and monitoring requirements for total iron of MCW, total copper of MCW, total recoverable copper and total recoverable iron are applicable only on any calendar day in which metal cleaning waste is discharged in the effluent from I-FG the Evaporator Condensate Storage Tank and/or the Condensate System.

4 Limitations apply to the effluents from outfall I-FG, ECST and the Condensate System Revised Page 6

DEPARTMENT OF ENVIRONMENTAL PROTECTION DISCHARGE MONITORING REPORT - PART A WHEN COMPLETED MAIL THIS REPORT TO: Department of Environmental Protection Wastewater Facilities Mgmt, MS 3551 2600 Blair Stone Rd, Tallahassee FL 32399-2400 PERMIT NUMBER: FLOO00159 Revision Date: 2/19/99 PERMITrEE NAME- Florida Power Corporation MONITORING PERIOD--From: To MAILING ADDRESS: P.O. Box 14042 LIMIT: Final REPORT: Monthly St Petersburg, Florida 33733 CLASS SIZE: Major GROUP: 1W FACILITY. Crystal River - Units 1,2, & 3 GMS ID NO.: 1037M25518 GMS TEST SITE NO.:

LOCATION US Highway 19 & Powerline Road, Crystal River, Florida 32629 DISCIIARGE POINT NUMBER: D-OF COUNTY Citrus (formerly OSN 006) NO DISCHARGE FROM SITE: E0 PLANT SIZE/TREATMENT TYPE:

A-13 DEP Form62-620 910(10), Effective November 29, 1994

W Statement of Basis For Minor Permit Revision Permit Number: FL0000159 Application Date: June 21, 2002 Permit Writer: Bala Nori Application No: FL0000159-008-IWB Name and Address of Applicant:

Florida Power Crystal River Plant Post Office Box 14042 Unitsl, 2 and 3 St. Petersburg Beach, Florida 33733 15760 W. Powerline Street Crystal River, FL 34428 The Department received a minor revision application from Florida Power dated June 21, 2002, requesting a reduction in monitoring frequency for Oil and Grease, Total Suspended Solids (at sampling Point EFF-7B) discharged to waters of State via outfall D-OF under the referenced permit.

The Department approves the reduction in monitoring frequency of Oil &Grease, Total Suspended Solids based on the application and on information provided by the applicant in response to the Department's request for additional information as follows:

1) The facility provided monitoring data for the period from 1/1/99 to 5/3/02 for Oil & Grease, and Total Suspended Solids,which are summarized as follows:

For Oil and Grease:

Average concentration in the Evaporator Condensate Storage Tank(ECST) prior to release into service water :3.8mg/1 For Total Suspended Solids:

Average concentration in the ESCT prior to release into service water: 1.0mg/I Frequency of discharge from ECST to the service water system is once every 2.3 days or approximately 3 discharges each week.

2) Based on the guidance memorandum provided by EPA titled "Interim Guidance for Performance Based Reduction of NPDES Permit Monitoring Frequencies", and dated April 19, 1996 the frequency of monitoring for Oil & Grease, Total Suspended Solids has been reduced from 1/Day of Discharge to 1/Week. The guidance memorandum indicates the ratio of long term average to monthly average is less than 25 percent, the monitoring frequency can be reduced from 3/week to 1/week for Oil and Grease, Total suspended Solids.