05000498/FIN-2008002-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | |
Description | The inspectors reviewed a self-revealing noncited violation of 10 CFR Part 50, Appendix B, Criteria III, for an inadequate design control package that resulted in incorrect instantaneous over current breaker trip point settings. On September 11, 2006, control room envelope heating, ventilation, and air conditioning make up Fan 11B failed to start due to an incorrect instantaneous over current breaker setting, set as part of Design Change Package 98-687-4. When the package was prepared the Class 1E design criteria that was in effect led the licensee to set the instantaneous over current breaker settings based on locked rotor nameplate data G motors. Because the locked rotor nameplate data of the motor control fed motors were not documented the licensee failed to identify that some of the motors were locked rotor nameplate data J motors. As a result, the breaker trip point setting was set too low leaving some motors susceptible to spurious tripping since the implementation of the change in 2000. Further investigation revealed several missed opportunities in previous years to identify the incorrect settings, resulted from human performance and program and process issues. There are no crosscutting aspects since the issue is greater than 2 years old and the licensees processes have changed considerably between 1998 and 2006. This finding was more than minor because it affected the Barrier Integrity attribute of structure, system, and component and barrier performance under maintaining the radiological barrier function of the control room and it affected the cornerstone objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events by maintaining the operational capability of the control room envelope heating, ventilation, and air conditioning boundary. Using the Significance Determination Process Phase 1 worksheets the finding was determined to have very low safety significance because the finding only represented a degradation of the radiological barrier function of the control room (Section 40A3) |
Site: | South Texas |
---|---|
Report | IR 05000498/2008002 Section 4OA3 |
Date counted | Jun 30, 2008 (2008Q2) |
Type: | NCV: Green |
cornerstone | Barrier Integrity |
Identified by: | NRC identified |
Inspection Procedure: | IP 71153 |
Inspectors (proximate) | J Dixon B Baca P Elkmann B Tharakan D Stearns C Johnson T Farnholtz M Hayes |
INPO aspect | |
' | |
Finding - South Texas - IR 05000498/2008002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (South Texas) @ 2008Q2
Self-Identified List (South Texas)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||