05000416/FIN-2008002-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Properly Implement a Compensatory Fire Watch Protection Procedures |
| Description | The inspectors identified a noncited violation of Facility Operating License Condition 2.C.41 for the failure to properly implement a compensatory fire watch per the station fire protection program. The inspectors performed a fire inspection of the auxiliary building electrical penetration room. The inspectors noted that plant personnel had not entered the room to perform a required fire watch. The inspectors questioned security personnel, reviewed the fire watch log and determined that the fire watch log had been checked off as completed. The completion time corresponded to the time an inspector was in the room. After further review and interviews with security personnel, the inspectors determined that the plant employee designated to perform the fire watch duties misunderstood the requirements for the fire watch. The employee had only verified the auxiliary building hallway area outside the room and failed to check inside the auxiliary building electrical penetration room as required. This issue was entered into the licensees corrective action program as Condition Report CR-GGN-2008-00869. The finding was more than minor since it was associated with the protection against external factors attribute of the reactor safety mitigating systems cornerstone, and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Using Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, the inspectors determined that the finding had an adverse affect on the \"Fixed Fire Protection Systems\" element of fire watches posted as a compensatory measure for outages or degradations. The inspectors assigned a high degradation rating due to the fact that the automatic fire suppression system was tagged out and inoperable. Because the system was degraded without compensatory actions for approximately 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, the inspectors used a duration factor of 0.01. The inspectors used 2E-2 for a generic fire frequency area which corresponds to Table 1.4.2, Generic Fire Area Fire Frequencies, for a switchgear room. The resulting calculated change in core damage frequency was 2E-4, which was greater than the high degradation Phase 1 Quantitative Screening Criteria of 1E-6, requiring a Phase 2 analysis. The inspectors consulted with a regional Senior Reactor Analyst and a simplified Phase 3 was performed using a duration factor of 2.3E-4 for the 2-hour time period, and the IPEEE specific room fire frequency of 7.2E-4. The resulting calculated change in core damage frequency was 1.7E-7, which would be less that the Phase 1 quantitative screening criteria. Using this information, the regional Senior Reactor Analyst, determined the finding to be of very low safety significance. The cause of this finding has a crosscutting aspect in the area of human performance associated with work practices in that the individual assigned to perform the fire watch proceeded in the face of uncertainty and failed to use appropriate human error prevention techniques H.4(a) (Section 1R05) |
| Site: | Grand Gulf |
|---|---|
| Report | IR 05000416/2008002 Section 1R05 |
| Date counted | Mar 31, 2008 (2008Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | R Deese P Elkmann R Smith A Barrett D Bollock |
| CCA | H.12, Avoid Complacency |
| INPO aspect | QA.4 |
| ' | |
Finding - Grand Gulf - IR 05000416/2008002 | |||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Grand Gulf) @ 2008Q1
Self-Identified List (Grand Gulf)
| |||||||||||||||||||||||||||||||||||||||||||||||||