05000395/FIN-2016004-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Promptly Identify and Correct a Condition Adverse to Quality for B Emergency Diesel Generator Exhaust Manifold Weld Indications |
Description | Green. A self-revealing, Green NCV of 10 CFR 50, Appendix B, Criterion XVI, "Corrective Action," was identified for the failure to promptly identify and correct a condition adverse to quality (CAQ) involving welded joint indications in the B emergency diesel generator (EDG) exhaust manifold. The licensee immediately removed the EDG from service to perform repairs, and the issue was entered into the licensees CAP as Condition Report CR-16-05421. The inspectors reviewed Inspection Manual Chapter (IMC) 0612, Appendix B, Issue Screening, dated September 7, 2012, and determined the PD was more than minor and therefore a finding, because it affected the Mitigating Systems Cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences and the respective attribute of equipment performance. Specifically, the B EDG was declared operable but degraded or nonconforming due to a circumferential weld failure and resulting separation of an exhaust manifold joint causing a small reduction in EDG power. The inspectors used IMC 0609, Significant Determination Process, Attachment 4, dated October 7, 2016, and Appendix A Exhibit 2, dated July 1, 2012, and determined the finding was of very low safety significance or Green because the finding was not a design deficiency or loss of function. The inspectors reviewed IMC 0310, Aspects Within Cross Cutting Areas, dated December 4, 2014, and determined the cause of this finding involved the cross-cutting area of problem identification and resolution and the aspect of resolution, P.3, because the licensee failed to take effective corrective actions commensurate with an issues safety significance in that they failed to promptly identify and correct a CAQ involving welded joint indications in the B EDG exhaust manifold. |
Site: | Summer |
---|---|
Report | IR 05000395/2016004 Section 1R15 |
Date counted | Dec 31, 2016 (2016Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | A Masters C Smith D Lanyi E Coffman G Ottenberg J Reece |
Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion XVI |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |
Finding - Summer - IR 05000395/2016004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Summer) @ 2016Q4
Self-Identified List (Summer)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||