05000389/LER-2008-003, Re Condensate Pump Failure Resulting in Manual Reactor Trip
| ML082321112 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie |
| Issue date: | 07/31/2008 |
| From: | Johnston G Florida Power & Light Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| L-2008-172 LER 08-003-00 | |
| Download: ML082321112 (4) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 3892008003R00 - NRC Website | |
text
- *.lt' 0
FPL Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 July 31, 2008 L-2008-172 10 CFR 50.73 1ý U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555 Re:
St. Lucie Unit 2 Docket No. 50-389 Reportable Event: 2008-003 Date of Event: June 7, 2008 Unit 2 Condensate Pump Failure Resulting in Manual Reactor Trip The attached Licensee Event Report 2008-003 is being submitted pursuant to the requirements of 10 CFR 50.73 to provide notification of the subject event.
Very t
- yours, Gor Jons on Site Vice President St. Lucie Plant GLJ/dlc Attachment IK-1 an FPL Group company
NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 08/31/201(
(9-2007)
Estimated burden per response to comply with this mandatory collection request: 50 hours5.787037e-4 days <br />0.0139 hours <br />8.267196e-5 weeks <br />1.9025e-5 months <br />. Reported lessons learned are incorporated into the licensing process and fed back to industry. Send comments regarding burden estimate to the Records and FOIA/Privacy Service Branch (T-5 LICENSEE EVENT REPORT (LER)
F52), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by intemet e-mail to infocollects@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
- 13. PAGE St. Lucie Unit 2 1
05000389 1
OF 3
- 4. TITLE Unit 2 Condensate Pump Failure Resulting in Manual Reactor Trip
- 5. EVENT DATE
- 6. LER NUMBER
- 7. REPORT DATE
- 8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR I SEQUENTIAL I REV MONTH D
Y I
NAME DOCKET NUIER NUMBER NO.
__MONTH DAY YEA_ i FACILITY NAME DOCKET NUMBER 06 07 2008 2008 -
003 00 07 31 2008
- 9. OPERATING MODE
- 11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply)
El 20.2201(b)
Ej 20.2203(a)(3)(i)
El 50.73(a)(2)(i)(C)
El 50.73(a)(2)(vii)
El 20.2201(d)
El 20.2203(a)(3)(ii)
El 50.73(a)(2)(ii)(A)
El 50.73(a)(2)(viii)(A)
El 20.2203(a)(1)
El 20.2203(a)(4)
El 50.73(a)(2)(ii)(B)
El 50.73(a)(2)(viii)(B)
El 20.2203(a)(2)(i)
El 50.36(c)(1)(i)(A) 0l 50.73(a)(2)(iii)
El 50.73(a)(2)(ix)(A)
- 10. POWER LEVEL E] 20.2203(a)(2)(ii)
El 50.36(c)(1)(ii)(A)
M 50.73(a)(2)(iv)(A)
El 50.73(a)(2)(x)
El 20.2203(a)(2)(iii)
El 50.36(c)(2)
El 50.73(a)(2)(v)(A)
El 73.71(a)(4) 100%
El 20.2203(a)(2)(iv)
El 50.46(a)(3)(ii)
El 50.73(a)(2)(v)(B)
[] 73.71(a)(5)
El 20.2203(a)(2)(v)
El 50.73(a)(2)(i)(A)
El 50.73(a)(2)(v)(C)
El OTHER El 20.2203(a)(2)(vi)
El 50.73(a)(2)(i)(B)
El 50.73(a)(2)(v)(D)
Specify in Abstract below or in
Corrective Actions
The corrective actions and supporting actions are entered into the site corrective action program.
Any changes to the proposed actions will be managed under the commitment management change program.
- 1. Revise motor rewind specification (SPEC-E-008) to ensure epoxy is not applied to the motor leads during the Vendor's vacuum pressure impregnationprocess.
- 2.
Revise motor rewind specification (SPEC-E-008) to add inspection hold points to inspect for epoxy and other contaminates.
Similar Events
A search of the corrective action database for St. Lucie was performed to identify events related to a condensate pump/reactor trip and none were found. This event is not considered a repeat event.
Failed Components Condensate Pump Motor; manufacture Allis-Chalmers - Machine Type "ANVOD"