05000353/LER-2011-005, Regarding Manual Actuation of the Reactor Protection System Due to Both Recirculation Pumps Trip

From kanterella
(Redirected from 05000353/LER-2011-005)
Jump to navigation Jump to search
Regarding Manual Actuation of the Reactor Protection System Due to Both Recirculation Pumps Trip
ML112082036
Person / Time
Site: Limerick 
(NPF-085)
Issue date: 07/27/2011
From: Maguire W
Exelon Generation Co, Exelon Nuclear
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER 11-005-00
Download: ML112082036 (5)


LER-2011-005, Regarding Manual Actuation of the Reactor Protection System Due to Both Recirculation Pumps Trip
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3532011005R00 - NRC Website

text

10CFR50.73 July 27, 2011 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Limerick Generating Station, Unit 2 Facility Operating License No. NPF-85 NRC Docket No. 50-353

Subject:

LER 2011-005-00, Manual Actuation of the Reactor Protection System Due to Both Reactor Recirculation Pumps Tripping This Licensee Event Report (LER) addresses an event that resulted in a manual actuation of the reactor protection system due to both reactor recirculation pumps tripping. The pumps tripped due to a failure of a main turbine first stage pressure instrument.

This LER is being submitted pursuant to the requirements of 10CFR50.73(a)(2)(iv)(A).

There are no commitments contained in this letter.

If you have any questions or require additional information, please do not hesitate to contact us.

Sincerely, Original signed by Peter A. Gardner for William F. Maguire Vice President - Limerick Generating Station Exelon Generation Company, LLC cc: USNRC Administrator Region I USNRC Senior Resident Inspector, LGS

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION (10-2010)

LICENSEE EVENT REPORT (LER)

(See reverse for required number of digits/characters for each block)

APPROVED BY OMB: NO. 3150-0104 EXPIRES: 10/31/2013

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

1. FACILITY NAME Limerick Generating Station, Unit 2
2. DOCKET NUMBER 05000353
3. PAGE 1 OF 4
4. TITLE Manual Actuation Of The Reactor Protection System Due To Both Recirculation Pumps Trip
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR SEQUENTIAL NUMBER REV NO.

MONTH DAY YEAR FACILITY NAME DOCKET NUMBER 05000 05 30 2011 2011 - 005 - 00 07 27 2011 FACILITY NAME DOCKET NUMBER 05000

9. OPERATING MODE 2
10. POWER LEVEL 0
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply) 20.2201(b) 20.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii) 20.2201(d) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(A) 20.2203(a)(1) 20.2203(a)(4) 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 20.2203(a)(2)(i) 50.36(c)(1)(i)(A) 50.73(a)(2)(iii) 50.73(a)(2)(ix)(A) 20.2203(a)(2)(ii) 50.36(c)(1)(ii)(A) 50.73(a)(2)(iv)(A) 50.73(a)(2)(x) 20.2203(a)(2)(iii) 50.36(c)(2) 50.73(a)(2)(v)(A) 73.71(a)(4) 20.2203(a)(2)(iv) 50.46(a)(3)(ii) 50.73(a)(2)(v)(B) 73.71(a)(5) 20.2203(a)(2)(v) 50.73(a)(2)(i)(A) 50.73(a)(2)(v)(C)

OTHER 20.2203(a)(2)(vi) 50.73(a)(2)(i)(B) 50.73(a)(2)(v)(D)

Specify in Abstract below or in LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET Component data:

Equipment:

Main Turbine First Stage Pressure Trip Unit Component Number:

PIS-001-2N652C Manufacturer:

R369 Rosemount Nuclear Instruments Inc.

Model Number:

510DU2