05000341/LER-2015-001, Regarding Secondary Containment Declared Inoperable After Loss of Reactor Building Ventilation from Freeze Protection Actuation
| ML15110A412 | |
| Person / Time | |
|---|---|
| Site: | Fermi (NPF-043) |
| Issue date: | 04/20/2015 |
| From: | Kaminskas V DTE Energy |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| NRC-15-0053 LER 15-001-00 | |
| Download: ML15110A412 (5) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(vi)(A) 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 3412015001R00 - NRC Website | |
text
Vito A. Kaminskas Site Vice President DTE Energy Company 6400 N. Dixie Highway, Newport, MI 48166 Tel: 734.586.6515 Fax: 734.586.4172 Email: kaminskasv@dteenergy.com DTE Energy-10 CFR 50.73 April 20, 2015 NRC-15-0053 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington D C 20555-0001
Reference:
Fermi 2 NRC Docket No. 50-341 NRC License No. NPF-43
Subject:
Licensee Event Report (LER) No. 2015-001 Pursuant to 10 CFR 50.73 (a)(2)(v)(C), DTE Electric Company (DTE) is submitting LER No. 2015-001, Secondary Containment Declared Inoperable after Loss of Reactor Building Ventilation from Freeze Protection Actuation.
No commitments are being made in this LER.
Should you have any questions or require additional information, please contact Mr.
Christopher R. Robinson of my staff at (734) 586-5076.
Sincerely, Vito A. Kaminskas Enclosure cc:
NRC Project Manager NRC Resident Office Reactor Projects Chief, Branch 5, Region III Regional Administrator, Region III Michigan Public Service Commission Regulated Energy Division (kindschlamichigan.gov)
Enclosure to NRC-15-0053 Fermi 2 NRC Docket No. 50-341 Operating License No. NPF-43 LER 2015-001, Secondary Containment Declared Inoperable after Loss of Reactor Building Ventilation from Freeze Protection Actuation
INRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPtRES: 0113112017 2-2014)
Estirated burden per response to comply with tis mandatory coiecion reouest: 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />.
Reported lessons 'earned are incoporaed ito he lcersing process and fed bck to Industry.
Send comments regarding burden estimate to the FOIA, Privacy and information ciections LICENSEE EVENT REPORT (LER) iosrc enrgo v Cnd t h ossin acr gtof C 2o555-:ormt or bn (See Page 2 for required number of Reguisory Affairs NEOS-10202 (3150-004), oCice o Mangemer an de, washingtonoc 20503. If a mens used to ompose an informaion oac tio d 'oes not disp.a a uretly vald oMB digits/characters for each block) contr onumber the NRC may not condc or sponrr,and s Person Is nor ep red to respond io the informaton collection.
- 3. PAGE Fermi 2 05000 341 1 OF 3
- 4. TITLE Secondary Containment Declared Inoperable after Loss of Reactor Building Ventilation from Freeze Protection Actuation
- 5. EVENT DATE
- 6. LER NUMBER
- 7. REPORT DATE
- 8. OTHER FACILITIES INVOLVED MONTH DAY YEAR YEAR MONTH DAY Y ARAFACUTYNAME OCKETNUMBER NUMSER NO 05000 T6 50CUTY NAME DOCKET NUMBER 02 19 15 15 001 0
04 P20 5S
- 9. OPERATING MODE
- 11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR @ (Check all that apply) 20.2201(b)
D 20.2203(a)(3)(i) 50.73(a)(2)(i)(C) 50.73(a)(2)(vii) 20.2201(d) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(A)
D 50.73(a)(2)(vi)(A) 20.2203(a)(1)
D 20.2203(a)(4)
Q 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 0 20.2203(a)(2)(i)
E 50.36(c)(1)(i)(A) 0 50.73(a)(2)(iii) 50.73(a)(2)(ix)(A)
- 10. POWER LEVEL D 202203(a)(2)(ii) 50.36(c)(1)(ii)(A)
I 50.73(a)(2)(iv)(A) 50.73(a)(2)(x) 20.2203(a)(2)(iii) 50.36(c)(2) 50.73(a)(2)(v)(A) 73.71 (a)(4) 20.2203(a)(2)(iv) 50.46(a)(3)(ii) 50.73(a)(2)(v)(B)
E]73.71(a)(5) 100 20.2203(a)(2)(v) 50.73(a)(2)(i)(A)
/
50.73(a)(2)(v)(C)
OTHER 20.2203(a)(2)(vi) 50.73(a)(2)(i)(B) 50.73(a)(2)(v)(D)
Speify in Abstract below or m
Initial Plant Conditions
Mode 1, 100 percent reactor power
Event Description
At 0303 EST on February 19, 2015, Fermi 2 experienced a trip of the non-safety related Reactor Building Ventilation (RBHVAC)
((VA)) during normal steady-state operations due to valid actuation of a freeze protection device. At the time of the trip, site area air temperature was -I degree Fahrenheit. The plant Technical Specifications (TS) require that Secondary Containment ((NG)) vacuum be maintained greater than or equal to -0.125 inches of water gauge. As a result of the RBHVAC trip, this specification was not maintained for approximately 4 seconds until the safety-related Standby Gas Treatment (SGT) system ((VA)) restored Secondary Containment vacuum to an acceptable value.
At 0324 EST, the tripped "H" Freeze-Stat was reset.
At 0335 EST, the West RBHVAC supply and exhaust fans were restored to operation.
At 0450 EST, the Division 1 SGTS was secured. As a result, Secondary Containment vacuum again degraded to less than -0.125 inches of water gauge for approximately 38 seconds until the SGTS was promptly re-actuated.
At 0458 EST, the East RBHVAC supply and exhaust fans were restored to operation.
At 0502 EST, the Division I SGTS was secured.
In both instances, the lowest observed vacuum was -0.11 inches of water gauge. There were no radiological releases associated with this event.
Safety Consequences and Implications
There were none. At no time during this event was there a potential for endangering the public health and safety.
The specified safety function of the Secondary Containment is to contain, dilute, and hold up fission products that may leak from primary containment following a Design Basis Accident (DBA). In conjunction with operation of the Standby Gas Treatment System (SGTS) and closure of certain valves whose lines penetrate the secondary containment, the secondary containment is designed to reduce the activity level of the fission products prior to release to the environment and to isolate and contain fission products that are released during certain operations that take place inside primary containment, when primary containment is not required to be OPERABLE, or that take place outside primary containment. It is possible for the pressure in the control volume to rise relative to the environmental pressure (e.g., due to pump and motor heat load additions.). To prevent ground level exfiltration while allowing the secondary containment to be designed as a conventional structure, the secondary containment requires support systems to maintain the control volume pressure at less than the external pressure. For the secondary containment to be considered OPERABLE, it must have adequate leak tightness to ensure that the required vacuum can be established and maintained.
During this particular event, the Secondary Containment vacuum degraded to a lowest value of -0.11 inches of water gauge for a maximum of 38 seconds. In Chapter 15 of the Fermi 2 UFSAR, RBHVAC is assumed lost at the onset of a LOCA concurrent with a Loss of Offsite Power. As a result, calculations show that the Secondary Containment would be pressurized until the SGTS restores vacuum. For this particular event, the Secondary Containment vacuum degraded when the non-safety related RBHIVAC system tripped due to freeze protection. The structural integrity (i.e., leak tightness) of the Secondary Containment was re-confirmed when the safety-related Division 1 SGTS restored vacuum to greater than -0.125 inches of water gauge. If the DBA LOCA for Secondary Containment concurrent with a Loss of Offsite Power had occurred during the time when Secondary Containment vacuum was between -0.11 and
- - 0.125 inches of water gauge, the Secondary Containment was sufficiently leak tight such that the SGTS would still have established and maintained vacuum greater than the TS required value.
(continued on next page)
NRC FORM 36A (02-2014)
(continued from previous page)
The radiological consequences of the DBA LOCA for Secondary Containment contained in Chapter 15 of the Fermi 2 UFSAR result in doses that are below 10CFR50.67. The Secondary Containment is assumed to be at a vacuum of -0.125 inches at the onset of the LOCA. For this particular event, had the DBA LOCA for Secondary Containment actually occurred, the increase in magnitude of radiological dose as a result of increased draw-down time from starting at -0.11 vice -0.125 inches of water gauge, would be minimal and negated by several very conservative assumptions in the existing analysis (e.g., 100% exfiitration from Secondary Containment during the first 15 minutes of drawdown with SGT in operation, 10% exfiltration from Secondary Containment with SGT in operation throughout the remaining 30 day duration of the accident, no holdup time in Secondary Containment throughout the 30 day duration of the accident, and all exfiltration and filtered releases are at ground level). These conservative assumptions are not reflective of actual plant conditions and configuration. This qualitative evaluation performed by the Fermi 2 Licensing and Engineering staff concludes that no actual loss of safety function occurred. This LER is required because the reporting threshold is "could have" prevented fulfillment of a safety fnction, which was valid at the time that Secondary Containment was declared INOPERABLE.
Cause of the Event
The RBHVAC system has 14 steam-supplied heating coils ((HCL)) and 14 corresponding low temperature switches (Freeze-Stat)
((TS)). The switches monitor the temperature of the air downstream of the heating coils to ensure the RBHVAC system does not freeze. If any single switch trips on low temperature, the RBHVAC system automatically trips. In this event, the "H" Freeze-Stat tripped on low temperature (35°F decreasing) and caused a trip of the RBHVAC system. A subsequent investigation concluded that the material properties of the "H" heating coil deviated from the original design and resulted in a lower rate of heat transfer. This particular "H" heating coil was installed in November 2011 and is made of a copper-nickel composition. The original "H" heating coil was pure copper, as are the other 13 heating coils currently installed. The reduced thermal conductivity of the copper-nickel material resulted in a reduced RBHVAC air temperature downstream of the "H" coil and actuated the "H" Freeze-State as designed. The Fermi 2 staff have documented the investigation and corrective actions in CARD 15-21350.
Corrective Actions
A work order has been generated to replace the "H" heating coil with original design specification material. The work order is scheduled to be completed before the next winter season.
Previous Occurrences
There have been 5 occurrences of Freeze-Stat actuations in the RBHVAC system between November 2014 and March 2015. This event is the only one that resulted in declaring the Secondary Containment INOPERABLE.
LER 2013-003: Secondary Containment was declared INOPERABLE after RBHVAC tripped due to Freeze-Stat actuation resulting from a failed steam trap.
LER 2013-001: Secondary Containment was declared INOPERABLE after RBHVAC dampers malfunctioned.
Note:
IEEE Standard Component and System Identifiers are indicated by the use of double brackets (( )).