| Title | Failure to evaluate fire penetration 1T43-H528J |
| Description | The NRC identified a Green Non-Cited Violation (NCV) of Unit 1 License Condition 2.C.(3) Fire Protection when a fire penetration that deviated from three-hour rating requirements was not evaluated in accordance with Unit 1 Fire Hazards Analysis (FHA) Appendix I, Evaluation of non-rated penetration seals in rated fire barriers. The licensee initiated roving fire watches and initiated corrective actions to restore compliance with Appendix I of the Unit 1 FHA. The violation was entered into the licensees corrective action program as CR 865615. Failure to implement the Unit 1 Fire Hazards Analysis (FHA) Appendix I, Evaluation of nonrated penetration seals in rated fire barriers was a performance deficiency. This performance deficiency was more than minor because it was associated with the Mitigating Systems cornerstone of the Protection Against External Factors (Fire) attribute and adversely affected the cornerstone objective in that the licensee failed to evaluate the asfound configuration of the penetration which resulted in a nonfunctional fire barrier. The inspectors determined the finding was Green because there was a fully functional automatic suppression system on either side of the fire barrier. The inspectors determined that thi
finding did not have an associated cross-cutting aspect because this finding is not reflectiv of current licensee performance. |
| Site: | Hatch |
|---|---|
| Report | IR 05000321/2014005 Section 1R05 |
| Date counted | Dec 31, 2014 (2014Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | B Caballero D Hardage D Lanyi D Retterer J Viera M Franke M Speck S Sanchez W Loo |
| Violation of: | License Condition - Fire Protection License Condition |