05000289/FIN-2008006-04
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Require Emergency Lighting Units (ELUs) (Section 4OA2.c.3) |
Description | The inspectors identified a NCV of License Condition 2.c(4) and 10 CFR 50, Appendix R, Section III.J, which require that emergency lighting units (ELUs) with at least an eight-hour battery power supply be provided in areas needed for operation of safe shutdown (SSD) equipment and in access and egress routes thereto. Specifically, Fire Hazards Analysis Report (FHAR) Attachment 3-7 specifies a post-fire safe shutdown (SSD) action for operators to manually operate valve IC-V-4 within four hours for a fire in fire zone AB-FZ-9, and ELUs were not provided at valve IC-V-4 and portions of the adjacent access and egress routes. The finding is more than minor because it was associated with the Mitigating Systems Cornerstone attribute of protection against external factors (i.e. fire) and affects the cornerstone objective of ensuring reliability and capability of systems that respond to initiating events. Specifically, the finding adversely affected to some degree the ability to carry out local operator actions required to achieve and maintain a SSD condition following a severe fire. This finding was of very low significance because it involved a low degradation of SSD capability. The conclusion of low degradation was based on the fact that the procedure step in question has a four hour completion time per FHAR Attachment 3-7. The finding has a cross-cutting aspect in the area of PI&R, Self and Independent Assessments Component, because AmerGen did not take the appropriate corrective actions to address this issue commensurate with its safety significance. Specifically, as part of an extent of condition review for missing ELUs identified by a fire safe shutdown self assessment conducted in 2003, AmerGen identifed that emergency lighting was needed at valve, IC-V-4, to meet the requirements of 10 CFR 50, Appendix R, but has not evaluated and corrected the issue in a timely manner. P.3(c) (Section 4OA2.c.3) |
Site: | Three Mile Island ![]() |
---|---|
Report | IR 05000289/2008006 Section 4OA2 |
Date counted | Jun 30, 2008 (2008Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | D Tifft M Gray J Brand G Newman |
CCA | P.6, Self-Assessment |
INPO aspect | CL.2 |
' | |
Finding - Three Mile Island - IR 05000289/2008006 | ||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Three Mile Island) @ 2008Q2
Self-Identified List (Three Mile Island)
| ||||||||||||||||||||||||||||||||||