05000237/FIN-2008008-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Develop a Pre-Fire Plan for Fire Zone 18.6 |
Description | The inspectors identified an NCV for the licensees failure to develop a pre-fire plan for fire zone 18.6. The finding was a violation of Dresden Nuclear Power Station Renewed Operating License. License conditions 2.E and 3.G for Unit 2 and Unit 3, respectively, of the Dresden Nuclear Power Station Renewed Facility Operating Licenses state, in part, that: The licensee shall implement and maintain in effect all provisions of the approved fire protection program as described in the Updated Final Safety Analysis Report (UFSAR) or the facility.... Pre-fire plans are described in the UFSAR as provided for all safety-related areas of the plant. Corrective actions by the licensee included the development of a pre-fire plan for fire zone 18.6. The finding was more than minor because it involved the Mitigating Systems attribute of protection against external factors (i.e. fire), where the failure to develop a pre-fire plan for fire zone 18.6 could have adversely impacted the fire brigades ability to fight a fire. As such, this finding impacted the Mitigating Systems objective to ensure availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. As discussed by IMC 0609, Appendix A, Attachment 0609.04, issues related to performance of the fire brigade are not included in IMC 0609, Appendix F, Fire Protection SDP, and require management review. Therefore, the finding was reviewed by NRC management, and was determined to be a finding of very low safety significance (Green) because no safe shutdown equipment was located in this fire zone. The inspectors determined that this issue also affected the cross-cutting area of problem identification and resolution, CAP aspect P.1(c) because the licensee failed to thoroughly evaluate a problem previously identified by NCV 05000237/2006011-01; 05000249/2006011-01, Licensees failure to develop a pre-fire plan for fire zone 8.2.6.A, elevation 534, such that the resolution did not fully address causes and extent of condition. (Section 4OA2.a) |
Site: | Dresden |
---|---|
Report | IR 05000237/2008008 Section 4OA2 |
Date counted | Mar 31, 2008 (2008Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | M Ring D Melendez A Barker D Schrum A Dahbur |
CCA | P.2, Evaluation |
INPO aspect | PI.2 |
' | |
Finding - Dresden - IR 05000237/2008008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Dresden) @ 2008Q1
| |||||||||||||||||||||||||||||||||||||||||||||||||||||