05000220/FIN-2013005-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Perform Surveillance Test for Unit 1 Smoke Removal Dampers |
| Description | The inspectors identified a Green NCV of Unit 1 license condition DPR-63, Section 2.D(7), Fire Protection, because CENG staff did not perform visual inspections of fire dampers associated with Unit 1 between 2002 and 2013 in accordance with the Fire Protection Program and Updated Final Safety Analysis Report (UFSAR) Section 10A.2.4.1.10.1.A. As a result, CENG staff determined 25 dampers were non-functional due to the surveillance test not being performed. CENG staffs planned corrective actions include revising the UFSAR to state that performance-based testing requirements apply only to non-smoke removal dampers. Further, the 25 smoke removal dampers will remain nonfunctional until visual inspections can be performed as planned in work order (WO) C92482273. This issue was entered into CENGs CAP as CR-2013-009208. This finding is more than minor because it is associated with the structure, system, and component (SSC) and barrier performance attribute of the Barrier Integrity cornerstone and affected the cornerstone objective of providing reasonable assurance that physical design barriers protect the operators in the control room from radionuclide releases caused by accidents or events. The finding was evaluated in accordance with IMC 0609.04, Initial Characterization of Findings, and Exhibit 3 of IMC 0609, Appendix A, The Significance Determination Process for Findings At-Power, issued June 19, 2012, and the inspectors determined that this finding is of very low safety significance (Green) because the performance deficiency only represented a degradation of the smoke removal and radiological barrier function provided for the control room. This finding has a cross-cutting aspect in the area of Problem Identification and Resolution, Corrective Action Program, because CENG staff failed to identify smoke removal damper visual inspections were not being performed. Specifically, UFSAR section 10A.2.4.1.10.1.A, as part of license condition DPR-63 2.D(7) and the Fire Protection Program, requires CENG staff to perform visual inspections of smoke removal dampers, which was not being performed between 2002 and 2013, resulting in the control room envelope not being operable and 25 smoke removal dampers being declared non-functional. CENG performed an evaluation to determine if the control room habitability requirements contained in TS 3.4.5.f for the control envelope were met. CENG staff subsequently determined that Unit 1 control room habitability requirements of TS 3.4.5.f were met based on previous successful surveillance testing for control room operability testing under N1-ST-C9, Control Room Emergency Ventilation System Testing, Revision 01502. |
| Site: | Nine Mile Point |
|---|---|
| Report | IR 05000220/2013005 Section 1R12 |
| Date counted | Dec 31, 2013 (2013Q4) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.12 |
| Inspectors (proximate) | B Dionne D Schroeder E Keighley E Miller H Gray J Deboer J Laughlin K Kolaczyk N Floyd S Hammann T Fish T Hedigan |
| Violation of: | Technical Specification License Condition - Fire Protection License Condition |
| CCA | P.1, Identification |
| INPO aspect | PI.1 |
| ' | |
Finding - Nine Mile Point - IR 05000220/2013005 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Nine Mile Point) @ 2013Q4
Self-Identified List (Nine Mile Point)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||