ENS 43290
ENS Event | |
---|---|
20:44 Apr 7, 2007 | |
Title | Fire in the Reactor Protection System Division 2 Equipment Room |
Event Description | On April 7, 2007 at 1330 Pacific Daylight Time (PDT) Columbia Generating Station (CGS) experienced an electrical fire in the Reactor Protection System (RPS) Division 2 equipment room. Currently, reactor level is stable and being controlled with the feedwater system. Reactor pressure is stable and being controlled with the turbine bypass valves in automatic. All safety systems are functional and there were no ECCS system actuations. At this time the plant is stable and the source of the fire was an electrical transformer which feeds the alternate electrical power supply to a Division 2 inverter isolation logic.
Plant operation was not impacted and the plant continues to operate at about 95% power. The first responder on-site extinguished the fire with a hand held fire extinguisher at about 1339 local time. The licensee has informed the NRC Resident Inspector.
The Emergency Action Level (EAL) entry condition for the Alert was a 'report by plant personnel of visible damage to equipment contained in a safe shutdown building' EAL 9.2.A.1. The equipment damaged was the backup power supply to the inverter. CGS has a fire watch established in the area to watch for reflash.
The Alert condition was terminated at 1721 PDT based on the fact that no reflash was seen by the fire watch, the extent of the equipment damage is understood and the area is now cool. Notified: R4DO (Cain), NRR EO (Haney), IRD Mgr. (Blount), R4 (Gwynn), DHS (Akers), FEMA (Sweetser), USDA (Jimenez), HHS (Dalziel), EPA (Natl. Resp. Cntr. - Crews). |
Where | |
---|---|
Columbia Generating Station Washington (NRC Region 4) | |
Reporting | |
Emergency class: | Alert |
10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
Time - Person (Reporting Time:+-3.3 h-0.138 days <br />-0.0196 weeks <br />-0.00452 months <br />) | |
Opened: | Jeff Gardener 17:26 Apr 7, 2007 |
NRC Officer: | Pete Snyder |
Last Updated: | Apr 7, 2007 |
43290 - NRC Website | |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (95 %) |
After | Power Operation (95 %) |
WEEKMONTHYEARENS 467392011-04-07T23:07:0007 April 2011 23:07:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hydrogen Burn During Maintenance ENS 452452009-08-05T14:50:0005 August 2009 14:50:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to Toxic Gas from a Switchgear Fire in the Turbine Building ENS 451692009-06-27T03:05:00027 June 2009 03:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Based on Fire Lasting Greater than 15 Minutes ENS 432902007-04-07T20:44:0007 April 2007 20:44:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Fire in the Reactor Protection System Division 2 Equipment Room ENS 424502006-03-28T21:57:00028 March 2006 21:57:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Range Brush Fire Near Plant ENS 417922005-06-24T06:21:00024 June 2005 06:21:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Licensee Declared an Unusual Event Due to Detection of a Flammable Gas in the General Services Building ENS 415652005-04-06T00:12:0006 April 2005 00:12:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Under E.A.L. 9-3.U.1 ENS 409102004-07-30T17:00:00030 July 2004 17:00:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared at Columbia Generating Station 2011-04-07T23:07:00 | |