05000456/FIN-2015001-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Adequately Evaluate Operability of a Degraded Control Room Chiller |
Description | The inspectors identified a finding of very low safety significance and an associated NCV of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, when licensee personnel failed to adhere to the operability determination process after identifying a degraded condition on the 0B control room chiller. This issue was entered into the licensees CAP as IR 2435363. The inspectors determined that the performance deficiency was more than minor in accordance with IMC 0612, Appendix B, Issue Screening, because it was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). Specifically, the licensee did not provide an adequate basis to support 0B control room chiller availability, reliability, and capability to respond to an initiating event. The inspectors determined that the finding was of very low safety significance because all questions related to structures, systems, and components (SSCs) and functionality in the associated significance determination process (SDP) were answered "No." The finding had a cross-cutting aspect in the Design Margins component of the Human Performance cross-cutting area because the licensee failed to adequately evaluate whether the degraded oil return line in the 0B control room chiller had sufficient margin to assure operability (H.6). |
Site: | Braidwood |
---|---|
Report | IR 05000456/2015001 Section 1R15 |
Date counted | Mar 31, 2015 (2015Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | B Boston D Betancourt E Duncan J Benjamin M Garza R Edwards T Go |
Violation of: | 10 CFR 50 Appendix B Criterion V |
CCA | H.6, Design Margins |
INPO aspect | WP.2 |
' | |
Finding - Braidwood - IR 05000456/2015001 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2015Q1
Self-Identified List (Braidwood)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||