- Information Notice 1994-56, Inaccuracy of Safety Valve Set Pressure Determinations Using Assist Devices (← links)
- 05000334/LER-1996-001-01, :on 960320,main Steam Valve Setpoints Not within Specification.Caused by Relatively Small Amount of Normal Setpoint Drift.C/A:Main Steam Safety Valve Adjustment Performed (← links)
- 05000334/LER-1995-004, :on 950301,five MSSV Determined by Testing to Be Outside TS 3.7.1.1 Tolerance of +1%-3%.Caused by Vendor Provision in Incorrect Mean Seat Area Data Used.Made Adjustments on Six Affected Safety Valves (← links)
- 05000272/LER-1995-026-01, :on 951023,main Steam Safety Valves Failed Lift Set Test.Caused by Use of Furmanite Trevitest Equipment That Had Inaccuracies.Rebuilt MSSV That Failed Lift Setpoint Test or Exceeded Allowable Seat Leakage Limits (← links)