- 05000409/LER-1979-019, Forwards LER 79-019/01T-0 (← links)
- 05000409/LER-1979-019-01, /01T-0:on 791223,periodic Leakage Rate Test for Emergency Airlock Did Not Meet Type B Test Criteria Specified by Tech Specs.Caused by Flattened O Rings & Shaft Packaging in Shaft Seal.Seal Replaced (← links)
- 05000409/LER-1979-009-03, /03L-0 on 790507:while Reactor Plant 125 Volt Dc Battery Was Removed for Maint,Control Power Key Switch Turned On.Procedural Change Will Be Initiated Requiring Use of Info Tag on Key Switch (← links)
- 05000409/LER-1979-009, Forwards LER 79-009/03L-0 (← links)
- 05000409/LER-1979-008-03, /03L-0 on 790429:during Periodic Type C Leakage Rate Testing,Containment Isolation Did Not Meet Tech Spec Criteria.Caused by Damper Disc Shaft Packing.Replaced W/Chevron Type Asbestos Composition Shaft Packing (← links)
- 05000409/LER-1979-008, Forwards LER 79-008/03L-0 (← links)
- 05000409/LER-1979-004-01, /01T-0 on 790119:indicated Leak Rate for Demineralized Water Isolation Valve Was 0.597 Std Cubic Ft/H.Caused by Normal Surface Wear.Valve Repaired & Now Complies W/Type C Test Criteria (← links)
- 05000409/LER-1979-003-01, /01T-0 on 790118:indicated Leakage Rate for Seal Injection Sys Makeup Valve Was 0.684 Std Cubic Ft/H.Cause Unknown.Valve Repaired,Now Complies W/Type C Test Criteria (← links)
- 05000409/LER-1979-010-03, /03L-0 on 790522:during Reactor Shutdown,Gross Alpha Activity of Primary Coolant Exceeded Tech Specs.Caused by Irradiated Fuel Matl in Rcs.Primary Purification Resins Replaced & Concentration Reduced (← links)
- 05000409/LER-1979-010, Forwards LER 79-010/03L-0 (← links)
- 05000409/LER-1979-001-01, /01L-0 on 790103:fuel Oil Samples from Tanks Indicated Water & Sediment Concentrations of 0.1%.Similar Occurrence RO-76-15.Tanks Resampled at 3 Elevations Prior to Partial Purging W/Levels Below 0.2% (← links)
- 05000409/LER-1979-001, Forwards LER 79-001/01L-0 (← links)
- 05000409/LER-1979-002-01, /01T-0 on 790115:periodic Leakage Rate Testing Revealed Electrical Penetration Units 3,4 & 6 Did Not Meet Type C Test Criteria.Imbrittlement of Epoxy Sealant Contributed to Leaks.Repaired W/Reapplication of Epoxy (← links)
- 05000409/LER-1979-002, Forwards LER 79-002/01T-0 (← links)
- 05000409/LER-1979-014-03, /03L-0 on 790708:during Power Escalation,Control Rod 10 Was Withdrawn Rather than Control Rod 12,placing Rods in out-sequence Condition.Caused by Operating Personnel Error.Compliance W/Program to Be Emphasized (← links)
- ML19259C802 (redirect page) (← links)
- 05000409/LER-1979-014 (redirect page) (← links)
- 05000409/LER-1979-013-03, /03L-0 on 790704:during Reactor Power Escalation, Piston Rod Seal Failure on Turbine Main Steam Bypass Valve Operating Cylinder Resulted in Loss of Hydraulic Oil.Caused by Normal Wear of Seal.Seals & Oil Replaced (← links)
- 05000409/LER-1979-013, Forwards LER 79-013/03L-0 (← links)
- 05000409/LER-1979-018-01, /01T-0:on 791214,util Notified by Allis-Chalmers That Containment Isolation Dampers Require Repositioning to Ensure Full Closure.Cause Not Stated.Dampers Closed Pending Allis-Chalmers Analysis.Ler to Be Updated (← links)
- 05000409/LER-1979-018, Forwards LER 79-018/01T-0 (← links)
- 05000409/LER-1979-011-03, /03L-0 on 790601:upscale Scram Setpoint on Power Range Nuclear Instrument Channel 6 Exceeded 120% Limit of Rated Thermal Power by 1.8%.Caused by Setpoint Drift of Undetermined Origin.Scram Setpoint Reset (← links)
- 05000409/LER-1979-011, Forwards LER 79-011/03L-0 (← links)
- 05000409/LER-1979-012-03, /03L-0 on 790702:during Operation,Test Revealed Pump A1 Failed to Start Upon Manual Actuation of Control Room Switch.Caused by Electrical Short Causing Diodes to Burn Out & Fuel Valve to Remain Closed.Diodes Replaced (← links)
- 05000409/LER-1979-012, Forwards LER 79-012/03L-0 (← links)
- 05000409/LER-1979-017-01, /01T-0:on 791109,reactor Vessel Cooled Down at Rate Exceeding Tech Specs During Reactor Scram.Caused by Turbine Governor Problem Resulting in Power to Flow Scram. Turbine Governor Sys Inspected & Flushed (← links)
- 05000409/LER-1979-017, Forwards LER 79-017/01T-0 (← links)
- 05000409/LER-1979-015-03, /03L:on 790822,during Normal Operation,Auxiliary Operator Commenced Pumping Retention Tank 1B to River,Rather than Sampling 4,500 Gallon Waste Tank.Pumping Stopped & Tank Sampled.No Radiological Release Limits Exceeded (← links)
- 05000409/LER-1979-015, Forwards LER 79-015/03L-0 (← links)
- 05000409/LER-1979-016-01, /01T-0:on 790907,during Low Recirculation Flow Scram,Bypass Key Switches Were Not Turned to Normal Position as Required by Tech Specs.Caused by Personnel Error.Addl Training Administered (← links)
- 05000409/LER-1979-016, Forwards LER 79-016/01T-0 (← links)