Pages that link to "05000333/LER-1981-053, Forwards LER 81-053/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000333/LER-1981-053, Forwards LER 81-053/03L-0:
Displayed 20 items.
- ML20009D655 (redirect page) (← links)
- 05000333/LER-1981-053-03, /03L-0:on 810625,mgt Review Revealed That Electric & Diesel Fire Pump Flow & Pressure Tests Per Tech Specs Were Not Conducted within Required Time Period.Caused by Failure to Place Surveillance Tests on Schedule.Tests Perfor (← links)
- 05000333/LER-1981-053 (redirect page) (← links)
- 05000333/LER-1981-054-03, /03L-0:on 810625,pressure Switch 02-3-PS-128A, Which Causes Isolation of Shutdown Cooling,Found Set Above Tech Spec Limit.Probably Caused by Instrument Drift.Switch Adjusted & Surveillance Frequency Increased (← links)
- 05000333/LER-1981-054, Forwards LER 81-054/03L-0 (← links)
- 05000333/LER-1981-046-03, /03L-0:on 810602,during Normal Operation,Personnel Noted Rod Block Monitor B Remained Bypassed When Control Rod Was Selected.Caused by Relay Failure.Relay Replaced (← links)
- 05000333/LER-1981-048-03, /03L-0:on 810604,during Normal Operation,Drywell Equipment Drain Sump Pump B Lost Suction.Cause & Corrective Action Will Be Determined at Future Plant Outage (← links)
- 05000333/LER-1981-047-03, /03L-0:on 810603,while Conducting Surveillance, Drywell Floor Drain Sump Flow Recorder & Square Foot Module Found Out of Calibr.Cause Not Stated.Calibr Corrected (← links)
- 05000333/LER-1981-044, Forwards LER 81-044/03L-0 (← links)
- 05000333/LER-1981-049, Forwards LER 81-049/03L-0 (← links)
- 05000333/LER-1981-025-03, /03L-0:on 810323,while Conducting Surveillance During Normal Operation,Reactor Water Level Switch Found Set Contrary to Tech Specs.Caused Attributed to Instrument Drift.Switch Adjusted & Weekly Surveillance Performed (← links)
- 05000333/LER-1981-025, Forwards LER 81-025/03L-0 (← links)
- 05000333/LER-1981-043-03, /03L-0:on 810526,portions of Emergency Diesel Generator Required Surveillance Found Performed on Monthly Plus 25% Basis During Part of Jan & Feb 1981.Caused by Administrative Error (← links)
- 05000333/LER-1981-043, Forwards LER 81-043/03L-0 (← links)
- 05000333/LER-1981-040-03, /03L-0:on 810505,RHR Flow Indicator 10-FI-133A Was Found Out of Calibr.Probably Caused by Instrument Drift. Indicator Recalibr (← links)
- 05000333/LER-1981-040, Forwards LER 81-040/03L-0 (← links)
- 05000333/LER-1981-037-03, /03L-0:on 810427,average Planar Linear Heat Generation Rate Surveillance Found Not Performed on 810420, 21 & 23 Per Tech Spec 4.5.H.Caused by Personnel Error. Personnel Will Review Event Rept to Prevent Recurrence (← links)
- 05000333/LER-1981-036-03, /03L-0:on 810422,motor on Low Pressure Coolant Injection Valve 10-MOV-25 Failed Rendering LPCI Loop a Inoperable.Caused by Motor Failure.Replacement of Motor Restored LPCI Loop a to Operable Status (← links)
- 05000333/LER-1981-029-03, /03L-0:on 810401,recirculation Pump a Coolant Leakage Exceeded Tech Spec.Caused by Seal Failure Due to Age.Seal Replaced (← links)
- 05000333/LER-1981-029, Forwards LER 81-029/03L-0 (← links)