- ML20003A930 (redirect page) (← links)
- ML20003A931 (← links)
- 05000333/LER-1981-002-03, /03L-0:on 810106,condensate Storage Tank Level Switches 23-LS-74B & 75B Did Not Operate as Required.Caused by Incorrect Setpoint Due to Moisture.Switches Cleaned, Lubricated & Recalibr (← links)
- 05000333/LER-1981-002, Forwards LER 81-002/03L-0 (← links)
- 05000333/LER-1981-016-03, /03L-0:on 810203,reactor Core Isolation Cooling Made Inoperable to Repair Thermocouple Connection in Subsys. Caused by Thermocouple Failure Due to Normal Wear & Tear. Connection Repaired (← links)
- 05000333/LER-1981-016, Forwards LER 81-016/03L-0 (← links)
- 05000333/LER-1981-017-03, /03L-0:on 810207,average Power Range Monitors a & E Downscale Trips Found Set at Less than 2.5/125,in Violation of Tech Spec 3.1-1.Possibly Caused by Instrument Drift.Downscale Trips Adjusted (← links)
- 05000333/LER-1981-017, Forwards LER 81-017/03L-0 (← links)
- 05000333/LER-1981-015, Forwards LER 81-015/03L-0 (← links)
- 05000333/LER-1981-014-03, /03L-0:on 810129,instrument Functional Surveillance Test of LPCI Cross Connect Valve Alarm Not Performed Per Tech Specs.Caused by Lack of Surveillance Test Procedure Due to Personnel Error.Test F-ST-2T Written (← links)
- 05000333/LER-1981-014, Forwards LER 81-014/03L-0 (← links)
- 05000333/LER-1981-012-04, /04L-0:on 810120,found Offgas Vent Pipe (Stack) Sample Pumps Had Been Off Since Loss of Instrumentation Power Resulting in Plant Hot Shutdown Condition.Caused by Design Deficiency.Sample Pumps Started (← links)
- 05000333/LER-1981-003-03, /03L-0:on 810106,containment Isolation Valve 16-1-AOV-102A Would Not Close.Caused by Natural End of Life. Valve Will Be Replaced (← links)
- 05000333/LER-1981-003, Forwards LER 81-003/03L-0 (← links)
- 05000333/LER-1981-002 (redirect page) (← links)
- 05000333/LER-1981-038-03, /03L-0:on 810428,during Normal Operation, Interchange of Drywell Equipment Drain & Floor Drain Data Was Discovered,As Result of Mgt Review.Caused by Personnel Error.Instrument Modules Were Placed in Proper Locations (← links)
- 05000333/LER-1981-039-03, /03L-0:on 810429,during Normal Operation,Trouble Shooting of Indicator Lamp Problem for Containment Spray Valves 10-MOV-26A & 31A Revealed Limit Switch Rotor Failure. Cause Unknown.Rotors Replaced.Evaluation Ongoing (← links)
- 05000333/LER-1981-039, Forwards LER 81-039/03L-0 (← links)
- 05000333/LER-1981-018-03, /03L-0:on 810209,steam Line High Flow Switches 02-DPIS-116A & 116B Were Found Outside Tech Spec.Probably Caused by Instrument Drift.Switches Calibr (← links)
- 05000333/LER-1981-009-03, /03L-0:on 810115,during Normal Operation, Administrative Review Noted Fire Hose Gasket Insp & Rerack Not Completed as Required by Tech Specs.Caused by Personnel Error.Improper Data Sheets Not Used After May 1980 (← links)
- 05000333/LER-1981-042-03, /03L-0:on 810518,offsite 115 Kv Supply Breaker 10022 Tripped & Failed to Auto Reclose.Caused by Line Fault. Power Source Restored (← links)
- 05000333/LER-1981-042, Forwards LER 81-042/03L-0 (← links)
- 05000333/LER-1981-041, Forwards LER 81-041/03L-0 (← links)
- 05000333/LER-1981-035-03, /03L-0:on 810418,erratic Operation of Main Steam Line Radiation Monitor B Caused Spikes & Scram Signals in One Reactor Protection Sys Subchannel.Caused by Loose Fuse. Loose Fuse Condition Corrected (← links)
- 05000333/LER-1981-035, Forwards LER 81-035/03L-0 (← links)
- 05000333/LER-1981-023-03, /03L-0:on 810225,reactor Water Level Instrument 02-3-LIS-101C Found Set Below Allowable Limits & on 810302 Instrument Found Above Allowable Limits.Cause for Both Failures Believed to Be Broken Switch Lock.Lock Repaired (← links)
- 05000333/LER-1981-023, Forwards LER 81-023/03L-0 (← links)
- 05000333/LER-1981-021-03, /03L-0:on 810219,core Spray Pipe Break Switch 14-DPIS-43A Found Set Above Tech Spec Limit.Caused by Instrument Drift.Surveillance Increased to Daily,Guide Valve Changed to More Conservative Set Point & Training Conducted (← links)
- 05000333/LER-1981-021, Forwards LER 81-021/03L-0 (← links)
- 05000333/LER-1981-020-03, /03L-0:on 810213,during Normal Operation,Hpci Controller Indicated Possible Controller Failure.Sys Declared Inoperable.Caused by Failure of Two Transistors in Amplifier.Controller Replaced & Returned to Svc (← links)
- 05000333/LER-1981-019-03, /03L-0:on 810210,during Normal Operation,Reactor Water Conductivity Exceeded Tech Spec 3.6.C.4 Limits.Caused by Addition of Caustic to Condensate Storage Tanks Due to Personnel Error.Two Condensate Storage Tanks Cleaned (← links)
- 05000333/LER-1981-019, Forwards LER 81-019/03L-0 (← links)
- 05000333/LER-1981-010-03, /03X-1:on 810117,HPCI Sys Did Not Automatically Operate at Rated Speed Upon Receipt of Auto Start Signal Following Reactor Scram & Isolation.Caused by Reactor Water Level Shrink.Speed & Discharge Pressure Increased (← links)
- 05000333/LER-1981-010, Forwards LER 81-010/03X-1 (← links)
- 05000333/LER-1981-034-03, /03L-0:on 810414,direct Indication of Drywell/ Torus Differential Pressure Not Available W/Containment Penetration Instrument Isolated.Caused by Computer Out of Svc Due to Dirty Printed Circuit Board Contacts (← links)
- 05000333/LER-1981-034, Forwards LER 81-034/03L-0 (← links)
- 05000333/LER-1981-032, Forwards LER 81-032/03L-0 (← links)
- 05000333/LER-1981-024-03, /03L-0:on 810323,drywell Equipment Drain Sump Pump B Lost Suction & Could Not Effect Sump Pump Out.Cause Unknown.Amend to Tech Spec Submitted (← links)
- 05000333/LER-1981-022-03, /03L-0:on 810220,review Revealed Torus Water Level Recorders Had Not Been Included in Calibr Program Per 800123 Tech Specs Change.Caused by Personnel Error.Recorders Checked & Calibr Will Be Performed Once Each Six Months (← links)
- 05000333/LER-1981-007-03, /03L-0:on 810113,during Normal Operation,Core Spray Pipe Break D/P Switches 14-DPIS-43A&B Found Set at 1.08 & 0.77.Caused by Instrument Drift.Switches Recalibr & Returned to Svc (← links)
- 05000333/LER-1981-007, Forwards LER 81-007/03L-0 (← links)
- 05000333/LER-1981-006-03, /03L-0:on 810112,during Normal Operation,Rod Block Monitor B Failed to Null When Control Rod Selected.Caused by Relay Failure Due to End of Natural Life.Relay Board Replaced & Monitor Returned to Svc (← links)
- 05000333/LER-1981-008-03, /03L-0:on 810114,during Normal Operation,Resident Inspector Noted That Daily Reactor Coolant Leakage Rate Not Calculated on 810113 Contrary to Tech Specs.Caused by Personnel Error.Leak Rate Calculated for 39-h Period (← links)
- 05000333/LER-1981-005-04, /04L-0:on 810112,annual Test of Offgas Automatic Isolation Not Performed as Required by Ets.Caused by Missed Surveillance Due to Conflict Between ETS & Operating Tech Specs.Surveillance Test Revised to Reflect ETS Requiremen (← links)
- 05000333/LER-1981-005, Forwards LER 81-005/04L-0 (← links)