Pages that link to "05000304/LER-1979-008, Forwards LER 79-008/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000304/LER-1979-008, Forwards LER 79-008/03L-0:
Displayed 50 items.
- 05000304/LER-1979-004, Forwards LER 79-004/03L-0 (← links)
- 05000304/LER-1979-008-03, /03L-0 on 790209:when Closing MSIV 2D for Steam Generator Cleanup,Valve Began to Close,Then Reopened.Caused by Failure of Both DC Solenoid Valves to Shift When Energized.After Exercise,One Valve Replaced (← links)
- ML19282B842 (redirect page) (← links)
- 05000304/LER-1979-008 (redirect page) (← links)
- 05000295/LER-1979-007-03, /03L-0 on 790204:OA Lake Discharge Tank Failed to Close Automatically When Activity Reached Setpoint.Caused by Faulty Electrical Relay.Contacts Cleaned & Relay Card Securely Reconnected.Monitor Functionally Tested & Verified (← links)
- 05000304/LER-1979-009-03, /03L-0 on 790210:MSIV Partially Opened.Hydraulic Pump Was Reenergized,Causing MSIV to Reclose.Cause Was Combination of Drain Valve Not Opening After MSIV Closure & Open Accumulator Leaking Gas (← links)
- 05000304/LER-1979-009, Forwards LER 79-009/03L-0 (← links)
- 05000304/LER-1979-010-03, /03L-0 on 790214:Channel 2LT-460 Greater than 6% from Channel 2LT-461.Caused by Transmitter Had Zero & Span Shifted.Zero Adjustment Made,Transmitter Conservative for High & Low Level Trips (← links)
- 05000304/LER-1979-010, Forwards LER 79-010/03L-0 (← links)
- 05000295/LER-1979-004-03, /03X-1 on 790112:inverter 114 Tripped & Could Not Be Reset;Hot Shutdown Not Reached within 4-h.Caused by Loose Contact in DC Breaker & Personnel Error in Late Start of Shutdown.Breaker Will Be Fixed,Personnel Reinstructed (← links)
- 05000295/LER-1979-004, Forwards LER 79-004/03X-l (← links)
- 05000295/LER-1979-066-03, /03L-0:on 790909,steam Flow Channel Found Indicating Lower than Redundant.Caused by Failed Oscillator Casket.Failed Oscillator Replaced,Transmitter Recalibr & Returned to Svc (← links)
- 05000295/LER-1979-066, Forwards LER 79-066/03L-0 (← links)
- 05000304/LER-1979-032-03, /03L-0 on 790508:after Reactor Trip,Train a Reactor Trip Breaker Failed to Open.Caused by Plunger Out of Adjustment in Undervoltage Coil (← links)
- 05000304/LER-1979-032, Forwards LER 79-032/03L-0 (← links)
- 05000295/LER-1979-032-03, /03L-0 on 790420:blower Tripped on Containment Vent Particulate Monitor,Resulting in Low Flow.Caused by Thermal Overload Due to Dust Blocking Pump Vent.Vent Cleaned & Monitor Tested & Returned to Svc (← links)
- 05000295/LER-1979-032, Forwards LER 79-032/03L-0 (← links)
- 05000304/LER-1979-031, Forwards LER 79-031/03L-0 (← links)
- 05000304/LER-1979-029-03, /03L-0 on 790423:during Change of Startup Batteries on 2C CS Pump,Spray Sys Was Inadvertently Rendered Inoperable W/O Performing Required Surveillance.Caused by Personnel Error in Operating multi-position Switch (← links)
- 05000304/LER-1979-029, Forwards LER 79-029/03L-0 (← links)
- 05000295/LER-1979-040-03, /03L-0 on 790523:during Periodic Testing,Steamline Isolation Signal Developed on Train A.Msiv 1B Failed to Close.Caused by Dc Solenoid Directional Control Valve Sticking in de-energized Position.Valve Replaced (← links)
- 05000295/LER-1979-041-03, /03L-0 on 790522:during Normal Operation Pressurizer Spray Valves Opened to 50% Demand & RCS Pressure Decreased Below Tech Spec Limit.Caused by Operator Bumping Potentiometer on Pressurizer Master Controller (← links)
- 05000295/LER-1979-041, Forwards LER 79-041/03L-0 (← links)
- 05000295/LER-1979-017-04, /04T-0 on 790314:boron Usage Exceeded Tech Spec Limits Between 790310 & 14.Caused by Drummed Radioactive Waste Consisting of Borated Water.Usage Has No Bearing on Water Quality Program (← links)
- 05000304/LER-1979-002-03, /03L-0 on 790107:during Surveillance,Bus 238 Transformer Feed Failed to Auto Reclose When re-energized. Caused by Dirty Relay Contacts (← links)
- 05000304/LER-1979-002, Forwards LER 79-002/03L-0 (← links)
- 05000295/LER-1979-002-03, /03L-0 on 790108:blower of 1RE-0011,containment Vent Particulate Monitor,Tripped.Caused by Fuse Failure in Control Room Monitor (← links)
- 05000295/LER-1979-005, Forwards LER 79-005/03L-0 (← links)
- 05000295/LER-1979-006, Forwards LER 79-006/01T-0 (← links)
- 05000295/LER-1979-009-03, /03L-0 on 780930:quarterly Average Gaseous Release Rate Was Twice Annual Objective But Less than Tech Spec Max. Caused by Reactor Headvent During Refueling & Conservative Quantification Methods (← links)
- 05000295/LER-1979-009, Forwards LER 79-009/03L-0 (← links)
- 05000295/LER-1979-003-01, /01T-0 on 790109:Westinghouse Results of Feb 1978 ECCS Model Analysis Determined That Fq Limit Should Be 1.86 Rather than the Current Limit of 2.02.Plant Operations Modified to Adhere to New Limit (← links)
- 05000295/LER-1979-003, Forwards LER 79-003/01T-0 (← links)
- 05000295/LER-1979-079-03, /03L-0:on 791023,during Refueling,Auxiliary Bldg Area Radiation Monitor Repeatedly Failed Low.Caused by Broken Restraining Clamp on Photomultiplier Tube.Clamp Replaced.Monitor Functionally Tested & Restored to Svc (← links)
- 05000295/LER-1979-076-03, /03L-0:on 791010,while Performing Refueling Surveillances,Reactor Coolant Flow Transmitter 1FT-444 Shifted High.Caused by Zero Shift.Transmitter Recalibr Using New Technique to Correct Drift & Zero Shift Problem (← links)
- 05000295/LER-1979-076, Forwards LER 79-076/03L-0 (← links)
- 05000295/LER-1979-051-03, /03L-0 on 790718:fuel Monitor 1RT-PR27 Failed Sporadically.Caused by Corroded Contact Pins in Control Room Module Connector.Pins Replaced W/No Further Repairs Required (← links)
- 05000295/LER-1979-051, Forward LER 79-051/03L-0 (← links)
- 05000295/LER-1979-012, Forwards LER 79-012/99X-0 (← links)
- 05000304/LER-1979-034-03, /03L-0 on 790511:following Testing of O Diesel Generator,Starting Air Sys Leak Bleed Down & Starting Air Receivers.Caused by Loose Cap Screws Holding Valve Seat to Seat Retainer.Valve Seat Replaced & Fastened Correctly (← links)
- 05000295/LER-1979-093-03, /03L-0:on 791225,radioactivity Analysis of Fire Sump Discharge Sample Was Overlooked While Units Were in Cold Shutdown.Caused by Personnel Error.Computerized Sys to Provide Daily Monitoring Will Be Implemented (← links)
- 05000295/LER-1979-093, Forwards LER 79-093/03L-0 (← links)
- 05000295/LER-1979-092-03, /03L-0:on 791206,during Refueling,Gas Decay Tank Rad Monitor ORT-PRO2B Alarmed When Indicator Needle Read Below Alarm Setpoint.Caused by Accidental Jarring of Module, Dislodging Needle from Jewel Bearing.Meter Replaced (← links)
- 05000295/LER-1979-091-03, /03L-0:on 791207,during out-of-svc Surveillance for Gas Decay Tank Cubicle Radiation Monitor ORT-PR02B,shift Grab Sample Not Taken.Caused by Negligence of Radioactive Protection Group.Shifts Reinstructed (← links)
- 05000295/LER-1979-094-01, /01T-0:on 791228,pH of Effluent from Waste Water Treatment Facility Measured in 4.1-4.77 Range.Caused by Acidic Solution Leak in Waste Neutralization Tank Via Bad Packing Glands.Tank Neutralized (← links)
- 05000295/LER-1979-094, Forwards LER 79-094/01T-0 (← links)
- 05000295/LER-1979-028, Cancelled (← links)
- 05000295/LER-1979-023, Cancelled (← links)
- 05000295/LER-1979-026, Cancelled (← links)
- 05000295/LER-1979-022, Cancelled (← links)