- 05000295/LER-1982-010-03, /03L-0:on 820302,containment Purge Exhaust (CPE) Isolation Valve 1RV-0003 Failed to Fully Close on Receipt of Automatic Closing Signal Generated from de-energization of CPE Radiation Monitors.Caused by Tygon Tubing Being Stu (← links)
- 05000295/LER-1982-010, Forwards LER 82-010/03L-0 (← links)
- 05000304/LER-1982-004-99, /99X-0:on 820315,during Monthly Reactor Protection Logic Testing (PT-5A),reactor Trip Relay RT-3XA Burned Up & Failed in Nonconservative Mode.Caused by Overheating. Relays Replaced w/125/130-volt Dc Relays (← links)
- 05000304/LER-1982-004, Forwards LER 82-004/99X-0 (← links)
- 05000295/LER-1982-007-03, /03L-0:on 820216 & 17,1D Steam Generator Pressure Channel 1P-535 Failed Sporadically While in Hot Shutdown. Cause Not Stated.Several Transmitter Components Replaced. Transmitters in Critical Applications to Be Evaluated (← links)
- 05000295/LER-1982-008-03, /03L-0:on 820219,auxiliary Bldg 592-ft Monitor Found Reading Full Scale Low & Not Responding to External Radiation Source.Caused by Dirty Printed Circuit Board for Sensor Element.Board Cleaned (← links)
- 05000295/LER-1982-008, Forwards LER 82-008/03L-0 (← links)
- 05000295/LER-1982-006-03, /03L-0:on 820218,while Purging U-1,recorder for Stack Gas Monitor Ort Pr 18A Found Not Responding to Rad Monitor Readings.Caused by Inoperable Recorder.Recorder Repaired & Procedures Revised to Verify Operability (← links)
- ML20042B383 (redirect page) (← links)
- 05000295/LER-1982-006 (redirect page) (← links)
- 05000295/LER-1982-005-01, /01T-0:on 820226,pieces of Nozzle Cover Hinges Found in 1B & 1D Steam Generator Primary Hot Legs Which Came from Cover Left in RCS During Spring 1981 Refueling Outage & Resulted in 4% Flow Reduction in Loop D,During 810413-0 (← links)
- 05000295/LER-1982-005, Forwards LER 82-005/01T-0.Detailed Analysis Encl (← links)
- 05000295/LER-1982-003-03, /03L-0:on 820119,during Periodic Testing,Rhr Pump 1B Suction Valve 1MOV-8700B Failed to Open Electrically. Caused by Tripped Thermal Overloads on Valve Breaker.Valve Manually Opened.Overloads Reset (← links)
- 05000295/LER-1982-003, Forwards LER 82-003/03L-0 (← links)
- 05000304/LER-1982-002-03, /03L-0:on 820118,boric Acid Concentration Read Higher than Allowable Tech Spec Limit.Caused by Erroneous Sample Indications Due to Dilution of Samples W/Primary Flushing Water Via Leaking Valve.Valve Repaired (← links)
- 05000304/LER-1982-002, Forwards LER 82-002/03L-0 (← links)
- 05000304/LER-1982-001, Forwards LER 82-001/03L-0 (← links)
- 05000295/LER-1982-002-99, /99X-0:on 820125,potential Problem Identified W/Horizontal Travelers,Size 3 Mfg by Corner & Lada Co. Travelers Could Become Deformed Under Certain Loading Conditions.Travelers Not Used at Facility (← links)
- 05000295/LER-1982-001-03, /03L-0:on 820112,discharge Damper on Oc Fan Found Failed Open W/Fan Off,Leaving Aircraft Fire Protection Sys for Auxiliary Bldg Air Supply Intake Inoperable.Caused by Frozen Bore in Air Operated Relay Valve (← links)
- 05000295/LER-1982-050, Forwards LER 82-050/03L-0 (← links)
- 05000295/LER-1982-040, Forwards Updated LER 82-040/99X-1 (← links)
- 05000304/LER-1982-029, Forwards LER 82-029/03L-0 (← links)
- 05000295/LER-1982-048-03, /03L-0:on 821213,blower Belt for Miscellaneous Vent Stack Monitor ORT-PR18 A&B Found Broken.Caused by Normal End of Life.Belt & Defective Relay in Instrument Fail Alarm Circuitry Replaced (← links)
- 05000295/LER-1982-048, Forwards LER 82-048/03L-0 (← links)
- 05000295/LER-1982-046-03, /03L-0:on 821203,while Disassembling Discharge Valve,Crosstie Valve Between Boric Acid Transfer Pumps 1A & 1B Found Leaking.Caused by Valve Normal End of Life.Repairs Completed & Pump 1A Returned to Svc (← links)
- 05000295/LER-1982-046, Forwards LER 82-046/03L-0 (← links)
- 05000295/LER-1982-031-03, /03L-0:on 820707,power Range Detectors Indicated Low by 46% of Span Nonconservatively,Changing Power Range High Flux Setpoints (25% & 109%).Caused by Miscalibr of Power Detectors.Detectors Readjusted (← links)
- 05000295/LER-1982-031, Forwards LER 82-031/03L-0 (← links)