- 05000295/LER-1978-078, Forwards LER 78-078/01L-0 (← links)
- ML20150E152 (redirect page) (← links)
- 05000295/LER-1978-109-03, /03L-0 on 781020:during Refueling Surveillance Noted That Steam Generator 1D Level Channel IL-538 Was 5% High,Exceeding 2% Loop Tolerance.Caused by Blocked Instru Line Leading to Transmitter.Line Subsequently Cleared (← links)
- 05000295/LER-1978-109, Forwards LER 78-109/03L-0 (← links)
- 05000295/LER-1978-082, Forwards LER 78-082/03L-0 (← links)
- 05000295/LER-1978-115-99, /99L-0 on 780314:subj Facil Did Not Possess Cert of Compliance for Packages for 12 Shipments of Radioactive matl.10CFR71.12 Had Been Misinterpreted to Apply to Hittman Nuclear Packages.Registered W/Nrc to Use Hittman Package (← links)
- 05000295/LER-1978-120-03, /03L-0 on 781027:5 Snubbers Which Had Empty Reserviors Were Proven Inoperable When Bench Tested.Caused by Hydraulic Fluid Leakage.Leakeage Sources:Reservoir Seals, Leaking Body Joints & Adjustment Screw Thread Seals (← links)
- 05000295/LER-1978-109-03, /03L-0 on 781020:during Refueling Surveillance Noted That Steam Generator 1D Level Channel IL-538 Was 5% High,Exceeding 2% Loop Tolerance.Caused by Blocked Instru Line Leading to Transmitter.Line Subsequently Cleared (← links)
- 05000295/LER-1978-109 (redirect page) (← links)
- 05000295/LER-1978-120, Forwards LER 78-120/03L-0 (← links)
- 05000295/LER-1978-107-03, /03L-0 on 781020:during Refueling Surveillance, Noted That Steam Generator 1B Level Channel 1L-548 Had Drifted Above Tech Spec Accuracy Limit.Caused by Instru Drift of Transmitter Instru Subsequently Recalibr (← links)
- 05000295/LER-1978-107, Forwards LER 78-107/03L-0 (← links)
- 05000295/LER-1978-110-03, /03L-0 on 781021:surveillance Level Xmtrs 950,951 for Accumulator a & 956,957 for Accum B Were Found Out of Tolerance Low.Caused by Instru Drift (← links)
- 05000295/LER-1978-110, Forwards LER 78-110/03L-0 (← links)
- 05000295/LER-1978-106-03, /03L-0 on 781020:during Refueling Outage Surveillance,Noted That Feed Water Flow Xmtr 1LT-531 Had Shifted in Excess of Tech Spec Limits.Caused by Transmitter Drift.Xmtr Recalibr & Channel Returned to Normal (← links)
- 05000295/LER-1978-106, Forwards LER 78-106/03L-0 (← links)
- 05000295/LER-1978-096-03, /03L-0 on 780904:channel 1L-537 Higher than 2 Redundant Channels Due to Steam Leak on Root Valve (3/4, Manual,Globe)On Sensing Line Xmtr.Channel Failed Again on 780908.Root Valve Replaced (← links)
- 05000295/LER-1978-096, Forwards LER 78-096/03L-0 (← links)
- 05000295/LER-1978-102-03, /03L-0 on 781006:Westinghouse Reported 0.5% Error in Apdms Limit Calculations Due to Roundoff & Addl Apparent Error Totaled 1.5%,creating Potential for Exceeding Apdms Limits.Caused by X.Xxx Format of Apdms Calculations (← links)
- 05000295/LER-1978-097, Forwards LER 78-097/03L-0 (← links)
- 05000295/LER-1978-091-03, /03L-0 on 780914: Damper Switching Sequence from Normal to Accident Mode Caused Pressure Differential in 1B Rcfc.Pressure Differential Caused Accident Inlet Damper Blades to Flex & Bend.Switching Sequence to Be Changed (← links)
- 05000295/LER-1978-094-03, /03L-0 on 780914:on a Phase a isolation,1FCV-PR24B & 1FCV-WD17A Failed to Close Placing Containment Isolation Sys in Degraded Mode.Caused by Asco 8320 Solenoid Valve Failing to Close Due to Oil in Instru Air (← links)
- 05000295/LER-1978-094, Forwards LER 78-094/03L-0 (← links)
- 05000295/LER-1978-092-03, /03L-0 on 780914:an Inadvertent SI Occurred When 1A Diesel Generator Was Started Due to Bent Plunger Spring Causing Failure of Engine Trip Lockout Solenoid Valve (Asco 8320).Valves Replaced & Springs Checked (← links)
- 05000295/LER-1978-092, Forwards LER 78-092/03L-0 (← links)
- 05000295/LER-1978-095-99, /99X-0 on 780914:shortly After Reactor Trip an Inadvertent Safety Injection Occurred from a False Delta P Steam Pressure Signal,Generated from Shock of Feedwater Hammer.No Damage Resulted from Safety Injection (← links)
- 05000295/LER-1978-122-03, /03L-0 on 781107:fuel Bldg Area Radiat Monitor ORE0005 Alarmed High Due to Erroneous Readings in Control Room & Local Readouts.Caused by Failed Gm Tube;Detector Replaced (← links)
- 05000295/LER-1978-122, Forwards LER 78-122/03L-0 (← links)
- 05000295/LER-1978-129-03, /03L-0 on 781206:Unit 1 Purge Exhaust Rad Monitor Was Incorrectly Valved.Identification of Personnel & Cause 1RTPR09 of Event Could Not Be Determined.Control Room Is Being Investigated (← links)
- 05000295/LER-1978-129, Forwards LER 78-129/03L-0 (← links)
- 05000295/LER-1978-121-03, /03L-0 on 781101:MSIV 1D from Train a Did Not Close When Signal Was Removed,Caused by Relay Plunger Sticking (← links)
- 05000295/LER-1978-121, Forwards LER 78-121/03L-0 (← links)
- 05000295/LER-1978-078-01, /01L-0:on 780818:possible Use of Atypical Weld Metal Discovered in Loop 4 of Reactor Pressure Vessel. Interim Heatup & Cooldown Curves Calculated & Used to Provide Adequate Conservatisms Until Issue Resolved (← links)
- 05000304/LER-1978-071, Forwards LER 78-071/03L-0 (← links)
- 05000304/LER-1978-064, Forwards LER 78-064/03L-0 (← links)
- 05000304/LER-1978-066-03, /03L-0 on 780925:pressurizer Level 2LT-459 Was Found to Be 6% Lower That the Other 2 Channels.No Cause Was Found for Failure (← links)
- 05000304/LER-1978-069, Forwards LER 78-069/03L-0 (← links)
- 05000304/LER-1978-065-03, /03L-0 on 780919:during Normal Oper,Channel 2L-547 Had Failed High & Assoc Bistables Were Tripped,Due to Faulty Xmtr(Level,Mode 13D2495K).XMTR Replaced W/Spare & Channel Recalibr (← links)
- 05000304/LER-1978-067-03, /03L-0 on781008:S/G Level Channel 2 LI-538 Was Found to Be Indicating 6% Higher than the Other 2 Channels. Caused by Dirt in Xmtr Sensing Lines & a Xmtr Oscillator PN805B27U01 Being Out of Tune (← links)
- 05000304/LER-1978-067, Forwards LER 78-067/03L-0 (← links)