Pages that link to "05000287/LER-1982-003, Forwards LER 82-003/01T-0.Detailed Event Analysis Encl"
Jump to navigation
Jump to search
The following pages link to 05000287/LER-1982-003, Forwards LER 82-003/01T-0.Detailed Event Analysis Encl:
Displayed 23 items.
- 05000270/LER-1982-004-01, /01T:on 820302,testing of HPI Nozzle Areas Revealed Loose 2A2 Thermal Sleeves & Cracks in Id of Safe End & Piping.Caused by Thermal Fatigue.Cracked Piping,Safe End & Thermal Sleeves Replaced (← links)
- 05000269/LER-1982-002-01, /01T-0:on 820222,control Operator Moved Group 8 Control Rods Into Tech Spec Restricted Area to Clear Core Axial Imbalance Alarm.Caused by Operator Error.Rod Position Corrected & Computer Alarms Modified to Include Group 8 (← links)
- 05000287/LER-1982-002-03, /03L-0:on 820210,reactor Protection Sys Channel B Hot Leg Temp Readings Were Lower than Those of Channels A,C & D.Caused by Failure of Liner Bridge in Input Circuitry for Channel B Indication.Bridge Replaced (← links)
- 05000287/LER-1982-002, Forwards LER 82-002/03L-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-003 (redirect page) (← links)
- 05000287/LER-1982-001-03, /03L-0:on 820128,channel B Borated Water Storage Tank Level Indication Declared Inoperable Due to Erratic Indication.Caused by Dirt & Oil in Level Indicator Booster Relay & High Thermostat Settings on Sys Heat Trace (← links)
- 05000287/LER-1982-001, Forwards LER 82-001/03L-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-003-01, /01T-0:on 820209,steam Generator Tube Leak of Approx 0.11 Gpm Was Indicated by Condensate Steam Air Ejector Offgas Radiation Monitor.Caused by Crack on Tube 74-2.Tube Stabilized & Plugged (← links)
- 05000269/LER-1982-001, Forwards LER 82-001/03L-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-004-01, /01T-0:on 820217,exam of Radiograph on Weld 85 on Isometric Drawing 11 Indicated Circumferential Void.Caused by Improper fit-up Weld & Insp During Initial Const.Section of Weld Replaced & Socket Welded to Coupling (← links)
- 05000269/LER-1982-004, Forwards LER 82-004/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-003-01, /01T-0:on 820202,video Insp of Fuel Assemblies Revealed Broken Holddown Springs on Batch 7 Fuel Assemblies 01K3,01JV & 01KX.Caused by fatigue-induced Cracking at Surface Flaw.Springs Will Be Replaced Before Reload (← links)
- 05000270/LER-1982-002-01, /01T-0:on 820122,three Core Support Assembly Thermal Shield Bolts Found W/Heads Broken Off & Shock Pad Y-2 Attachment Bolts Discovered Broken.Caused by Intergranular Stress Corrosion Cracking.Pad Removed (← links)
- 05000270/LER-1982-001-01, /01T-0:on 820117,reactor Bldg Equipment Hatch Found Leaking Air Through Gap in Seal.Caused by Personnel Not Verifying Good metal-to-gasket Seal Had Been Made. Procedures Revised to Require Verification of Proper Seal (← links)
- 05000270/LER-1982-001, Forwards LER 82-001/01T-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-020-03, /03L-0:on 821214,both Unit 1 Turbine Driven & 1A Motor Driven Emergency Feedwater Pumps Incapable of Automatic Actuation for 60 S.Caused by Defective Procedures. Personnel Counseled & Procedures Rewritten (← links)
- 05000269/LER-1982-020, Forwards LER 82-020/03L-0.Detailed Event Analysis Encl (← links)
- 05000269/LER-1982-019-03, /03L-0:on 821207,valve 1HP-25 Failed to Open Remotely During Operational Valve Function Test.Caused by Component Failure.Valve Manually Cracked Open,Cycled & Stroke Tested (← links)
- 05000269/LER-1982-018-01, /01T-0:on 821014,three of Six Installed Safety Valves Determined to Have Degraded Performance Based on Valve Ring Settings.Cause of Difference in Ring Settings Unknown.Valves Reset Using EPRI Tested Settings (← links)
- 05000269/LER-1982-018, Forwards LER 82-018/01T-0.Detailed Event Analysis Encl (← links)
- 05000270/LER-1982-011-03, /03L-0:on 820822,erratic Indication Observed on Channel a Borated Water Storage Tank Level Instrumentation. Caused by Boiling Water in Level Transmitter Line.Heat Tracing Disconnected & Transmitter Lines Refilled (← links)
- 05000270/LER-1982-011, Forwards LER 82-011/03L-0.Detailed Event Analysis Encl (← links)
- 05000287/LER-1982-009, Forwards LER 82-009/01T-0.Detailed Event Analysis Encl (← links)