VraoxxxA Ex.ncTaxc ann Powna COMPANY Rxcnxown.VxnouxxA 23261 December 28, 1979 Mr. James P. O'Reilly, Director Serial No. 1160 Office of Inspection and Enforcement P0/RMB:suv U.S. Nuclear Regulatory Commission Docket No. 50-338 Region II License No. NPF-4 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303
Dear Mr. O'Reilly:
Pursant to North Anna Power Station Technical Specifications, the Virginia Electric and Power Company submitted Licensee Event Report No. LER-79-149/01T-0 dated November 15, 1979. The report indicated that the Safeguards Area Exhaust System which provides post LOCA ambient cooling for the Recirculation Spray and Lov Bead Safety Injection Pumps is not entirely seismically designed as stated in FSA2 Section 9.4.6.1.
The original design of the system scened to be in contrast to the FSAR criteria since the fan discharge ductwork up to and including the ventilation stack is not designed to Seisuic Category I require-ments.
Further evaluation of the design criteria as stated in the FSAR indicates, however, that the systen design basis is not contrary to the description con-tained in the FSAR. Specifically, FSAR Section 9.4.6.1 states that:
" Spaces containing the recirculation spray and safety injection pumps and their valve rooms are subject to potential radioactive contamination from gland leakage, and consequently their exhaust systen is designed for seismic Category I..."
The portion of the Safeguards Area Exhaust System designed to Seismic Category I requirements is described in detail in Table 3.2.1-1.
The table clearly in-dicates that only the Safeguards Area Ventilation Exhaust Fans and exhaust ductwork up to the fans are Seismic Category I.
'"he seismic design categories for all parts of the Enginee red Safety Feature Area Ventilation System is further described in the Supplement to the FSAR in response to Comment 9.44.
The response states that:
'*The entire Engineered Safety Feature (Safeguards) Area exhaust sys-tem, including the ducts and fans in the auxiliary building are de-signed to Seismic Class I requirements."
The entire system referred to in the response should be interpreted as the exhaust fans and the ductwork up to the fans as defined in Table 3.2.1-1 re-ferenced above.
The exhaust from the Safeguards Area fans discharge into a common ventilation duct along with the exhausts free several other plant7 areas.
1675 003 k?
P00ROR8lNAL 001080
/
..-s..
I
~
Mr. James P. O'Refily, Director The Seismic Category I ductverk is also shown in the Supplement to the FSAR in response to Corusent 9.85.
Figure 59.86-1 indicates that the exhaust ductwork from the Safeguards Area Fans as well as exhaust ductwork from other poten-i tially contaminated area fans up to and including the Ventilation Stacka are not designed to Seismic Category I requirements.
It is therefore concluded that the design of the Safeguards Ares Ventilation System is not in conflict with the system description or design basis contained in the FSAR as reported j
in License Event Report 1.ER-79-149/01T-0.
1 I
The exhaust ductvork from the Safeguards Area ventilation fans and other fans l
ventilating potentially contaminated areas up to and including tha ventilation stacks was not designed to Seismic Category I requirements, since it was assumed that a postulated failure of the fan discharge ductwork would result in a break in the exhaust ductwork rather than a crimp or full closure of the exhaust path.
Under the assumed failure mechanism, the Ventilation System would still perform its required function of providing adequate cooling of f
Engineered Safeguards equipeent.
Further evaluation of this design basis in-dicates that we cannot show conclusively by analysis that the exhaust ductwork frcm the fans up to and including the ventilation stack will not fail by crir: ping during a seisnic event. Therefore, a review has been conductM to determine what equipment required to mitigate the consequences of a LOCA might not receive adequate cooling assuming a loss of ventilation due to crimping of the non-seismic exhaust ductvork.
It was concluded that the outside recircu-lation spray pumps and the low head safety injection pu=ps ventilated by the Safeguards Area exhaust fans and the charging pumps ventilated by the Auxiliary Building Central Area exhaust fans are the only essential equipment that might not receive adequate cooling during this postulated event.
The Safeguards Area Ventilation Syste= is provided with an emergency supply system designed as Seismic Class I.
This system may be manually initiated following a loss of normal ventilation flow.
Therefore, adequato protection exists to ensure that equipexnt in this area can be adequately cooled during the postulated failure in tbo ventilation exhaust system.
However, there is no present neans of providing emergency backup ventilation for the charging pu=ps.
Since we are unable to prove by analysis that the Ventilation System is ade-quate to provide the necessary cooling requirements for the charging pumps, and since there is no seismically qualified backup emergency cooling, we plan to codify the Auxiliary Building Central Area Ventilation Exhaust System to ensure operability following a seismic event. The modification will consist of installing a mechanical means of opening the Central Area exhaust ductwork on the Auxiliary Building roof and seismically supporting the exhaust ductwork from the Central Area fans up to and including the new exhaust port. Should ventilation flow be lost by cri= ping downstream of this exhaust port, the ex-haust port vill be opened and ventilation flow re-established.
The exhaust from this path can be monitored by lining up the existing ventilation Vent Sampler radiation monitor to the Auxiliary Building Central Area exhaust.
This modification will be implemented as soon as possible.
The current pro-jected completion date is January 15, 1980 provided suitable materials are i
available.
l According to our current schadule for start-up of Unit No.1, the unit vill be i
returned to service prior to completion of this modification.
It is our in-pcr " t t ti tent, therefore, to complete the nodification during W Oh ki'l.
1675 004
-.<-s.
s Mr. James P. O'Reilly, Director No. 1.
Station emergency procedures will be revised as necessary to reflect the required operator actions to maintain ventilation flow following the postu-lated failure of the non-seismic ductwork. We vill continue our evaluation of the Ventilation System design basis to determine what other long term correc-tive action is necessary, if any, to ensure the adequacy of the system to pro-vide the required cooling to all Engineered Safeguards equipment.
In summary, although the original design basis is not in conflict with FSAR criteria, we cannot show analytically that the exhaust ductwork from the Safe-guards Area exhaust fans and the Auxiliary Building Central Area exhaust fans vill be adequate to ensure an operable flow path following a seismic event.
Therefore, corrective action will be taken as described above.
We would appreciate your prompt review and response on this matter.
Very truly yours.
,/ J r < u,-
C.11. Stallings Vice President - Power Supply And Production Operations RMB/suv:1N3 Enclosures (3 copies) cc:
Mr. Victor Stello, Director Office of Inspection and Enforcement P00R ORGINAL 1675 005
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000338/LER-1979-001-01, /01T-0 on 790115:non-conservatism Identified in Calculations Performed in Monitoring Axial Power Distribution Fj(Z).Caused by Omission of Sys & Procedures Used to Monitor Fj(Z) | /01T-0 on 790115:non-conservatism Identified in Calculations Performed in Monitoring Axial Power Distribution Fj(Z).Caused by Omission of Sys & Procedures Used to Monitor Fj(Z) | | | 05000338/LER-1979-001, Forwards LER 79-001/01T-0 | Forwards LER 79-001/01T-0 | | | 05000338/LER-1979-002, Forwards LER 79-002/03L-0 & 79-003/03L-0 | Forwards LER 79-002/03L-0 & 79-003/03L-0 | | | 05000338/LER-1979-002-03, /03L-0 on 790101:during Normal Operation,Pump 1-RM-P-159A Tripped on Overload.Containment Particulate Sample Flow Was Lost,Rendering Inoperable 1 Reactor Coolant Leak Detection Sys,Due to Deficient Federal 1206LLT Bearing | /03L-0 on 790101:during Normal Operation,Pump 1-RM-P-159A Tripped on Overload.Containment Particulate Sample Flow Was Lost,Rendering Inoperable 1 Reactor Coolant Leak Detection Sys,Due to Deficient Federal 1206LLT Bearing | | | 05000338/LER-1979-003-03, /03L-0 on 790102:during Periodic Test,Noted That Containment Isolation Valve TV-SV-102-1 Would Not Shut Fully.Cause Undetermined | /03L-0 on 790102:during Periodic Test,Noted That Containment Isolation Valve TV-SV-102-1 Would Not Shut Fully.Cause Undetermined | | | 05000338/LER-1979-004-03, /03L-0 on 790108:during 1-PT-36-1(A) Found That Steam Generator 3 Hi Hi Level Test Panel Was Faulty, Preventing Test of This Channel.Caused by Faulty Universal Logic Card on Test Panel | /03L-0 on 790108:during 1-PT-36-1(A) Found That Steam Generator 3 Hi Hi Level Test Panel Was Faulty, Preventing Test of This Channel.Caused by Faulty Universal Logic Card on Test Panel | | | 05000338/LER-1979-005-01, /01T-0 on 790129:mufflers for Emergency Diesel Generators Not Seismically Supported Nor Missile Protected as Required by Fsar.Caused by Const Error | /01T-0 on 790129:mufflers for Emergency Diesel Generators Not Seismically Supported Nor Missile Protected as Required by Fsar.Caused by Const Error | | | 05000338/LER-1979-005, Forwards LER 79-005/01T-0 & 79-008/01T-0 | Forwards LER 79-005/01T-0 & 79-008/01T-0 | | | 05000338/LER-1979-006-03, /03L-0 on 790111:damaged Wiper Seal Found on Hydraulic Suppressor 1-FW-HSS-233.Caused by Poppet Valves Which Control Lock Up Rate Being Improperly Set.Suppressor Replaced W/Operable Spare Suppressor.No Danger to Public | /03L-0 on 790111:damaged Wiper Seal Found on Hydraulic Suppressor 1-FW-HSS-233.Caused by Poppet Valves Which Control Lock Up Rate Being Improperly Set.Suppressor Replaced W/Operable Spare Suppressor.No Danger to Public | | | 05000338/LER-1979-006, Forwards LER 79-006/03L-0 | Forwards LER 79-006/03L-0 | | | 05000338/LER-1979-007-03, /03L-0 on 781116:during Normal Operation,Fire Door S54-5 Between Unit 1 Emergency Switchgear Room & Cable Vault Was Sprung & Would Not Make a Tight Seal,Evidently Due to Attempt to Free It While Stuck | /03L-0 on 781116:during Normal Operation,Fire Door S54-5 Between Unit 1 Emergency Switchgear Room & Cable Vault Was Sprung & Would Not Make a Tight Seal,Evidently Due to Attempt to Free It While Stuck | | | 05000338/LER-1979-008-01, /01T-0 on 790129:design Flow of 37 Gpm to Charging Pump Coolers Could Not Be Met.Caused by 2 Inch Carbon Steel Piping & Charging Pump Skid Piping Being Too Large to Allow Adequate Flow | /01T-0 on 790129:design Flow of 37 Gpm to Charging Pump Coolers Could Not Be Met.Caused by 2 Inch Carbon Steel Piping & Charging Pump Skid Piping Being Too Large to Allow Adequate Flow | | | 05000338/LER-1979-009, Forwards LER 79-009/03L-0 | Forwards LER 79-009/03L-0 | | | 05000338/LER-1979-009-03, /03L-0 on 790212:during Normal Operation,Snubber Support for C Steam Generator Atmosphere Discharge Line Found Damaged.Caused by Use of Support as Anchor for Chain Fall.Support Replaced | /03L-0 on 790212:during Normal Operation,Snubber Support for C Steam Generator Atmosphere Discharge Line Found Damaged.Caused by Use of Support as Anchor for Chain Fall.Support Replaced | | | 05000338/LER-1979-010-03, /03L-0 on 790127: During Calibr of Containment Particulate Monitor RMS159 in Mode 1, Instrument Read Low for Known Radiation Level. Caused by Detector High Voltage Setting Being Set Too Low | /03L-0 on 790127: During Calibr of Containment Particulate Monitor RMS159 in Mode 1, Instrument Read Low for Known Radiation Level. Caused by Detector High Voltage Setting Being Set Too Low | | | 05000338/LER-1979-011, Forwards LER 79-011/03L-0 | Forwards LER 79-011/03L-0 | | | 05000338/LER-1979-011-03, /03L-0 on 790126:fire Door SS54-9 Was Nonfunctional.Caused by Removal of Latch from Door by Person or Persons Unknown | /03L-0 on 790126:fire Door SS54-9 Was Nonfunctional.Caused by Removal of Latch from Door by Person or Persons Unknown | | | 05000338/LER-1979-012-03, /03L-0 on 790127: Unidentified Primary Coolant Leakage Greater than 5 Gpm Noted. Caused by Blown Packing on Residual Heat Removal Isolation Valve MOV-1700 & Packing Leak on Pressurizer Spray Valve PCV-1455A | /03L-0 on 790127: Unidentified Primary Coolant Leakage Greater than 5 Gpm Noted. Caused by Blown Packing on Residual Heat Removal Isolation Valve MOV-1700 & Packing Leak on Pressurizer Spray Valve PCV-1455A | | | 05000338/LER-1979-013-03, /03L-0 on 790214:during Normal Operation,Fire Door S71-7 Between Auxiliary Bldg & Health Physics Found non- Functional.Caused by Bent Phaser on Left Door.Phaser Taped Out of Way & New Phaser Installed | /03L-0 on 790214:during Normal Operation,Fire Door S71-7 Between Auxiliary Bldg & Health Physics Found non- Functional.Caused by Bent Phaser on Left Door.Phaser Taped Out of Way & New Phaser Installed | | | 05000338/LER-1979-014-03, /03L-0 on 790202:pressurizer Level Indicator Indicated High Over Allowable Range.Caused by Voltage Drift in Associated Level Transmitter.Appropriate Channel Placed in Trip Condition & Transmitter Recalibr | /03L-0 on 790202:pressurizer Level Indicator Indicated High Over Allowable Range.Caused by Voltage Drift in Associated Level Transmitter.Appropriate Channel Placed in Trip Condition & Transmitter Recalibr | | | 05000338/LER-1979-014, Forwards LER 79-014/03L-0 | Forwards LER 79-014/03L-0 | | | 05000338/LER-1979-015-03, /03L-0 on 790204:rod F08 Indicators in Disagreement.Caused by Voltage Drift in Signal Conditioning Card.Card Recalibrated & Functional Checks Performed Satisfactorily | /03L-0 on 790204:rod F08 Indicators in Disagreement.Caused by Voltage Drift in Signal Conditioning Card.Card Recalibrated & Functional Checks Performed Satisfactorily | | | 05000338/LER-1979-015, Forwards LER 79-015/03L-0 | Forwards LER 79-015/03L-0 | | | 05000338/LER-1979-016, Forwards LER 79-016/03L-0 | Forwards LER 79-016/03L-0 | | | 05000338/LER-1979-016-03, /03L-0 on 790213:main Steam trip,TV-MS-111A,valve Opened to Only 75% Capacity.Caused by Improperly Positioned Needle Valve Which Supplied Air to Valve Actuator.Valve Repositioned & Operation Restored | /03L-0 on 790213:main Steam trip,TV-MS-111A,valve Opened to Only 75% Capacity.Caused by Improperly Positioned Needle Valve Which Supplied Air to Valve Actuator.Valve Repositioned & Operation Restored | | | 05000338/LER-1979-017, Forwards LER 79-017/01T-0 | Forwards LER 79-017/01T-0 | | | 05000338/LER-1979-017-01, /01T-0 on 790212:during Axial Power Distribution Monitoring Sys Failure on 790206,FQ Survey Computer Program Could Not Monitor Axial Power Distribution.Caused by Incorrect Power Inputs from Process Computer | /01T-0 on 790212:during Axial Power Distribution Monitoring Sys Failure on 790206,FQ Survey Computer Program Could Not Monitor Axial Power Distribution.Caused by Incorrect Power Inputs from Process Computer | | | 05000338/LER-1979-018-03, /03L-0 on 790214:during Mode 1 Operation at 98% Power,Main Steam Trip Valve 1-TV-MS-111B Leaked Excessively & Was Isolated for Repair.Caused by Deteriorated Internal Gasket.Valve Isolated & Gasket Replaced | /03L-0 on 790214:during Mode 1 Operation at 98% Power,Main Steam Trip Valve 1-TV-MS-111B Leaked Excessively & Was Isolated for Repair.Caused by Deteriorated Internal Gasket.Valve Isolated & Gasket Replaced | | | 05000338/LER-1979-019-03, /03L-0 on 790216:during Surveillance,Emergency Diesel Generator 1H Did Not Reach 900 Revolutions Per Minute in Required 10-s.Probable Cause Was Low Ambient Air Temp. Conditions of First Start Were Not Reproducible | /03L-0 on 790216:during Surveillance,Emergency Diesel Generator 1H Did Not Reach 900 Revolutions Per Minute in Required 10-s.Probable Cause Was Low Ambient Air Temp. Conditions of First Start Were Not Reproducible | | | 05000338/LER-1979-020-03, /03L-0 on 790131:fire Door S54-9 Was Found to Be non-functional.Caused by Recently Installed Electric Door Strike Slipping Out of Adjustment | /03L-0 on 790131:fire Door S54-9 Was Found to Be non-functional.Caused by Recently Installed Electric Door Strike Slipping Out of Adjustment | | | 05000338/LER-1979-020, Forwards LER 79-020/03L-0 | Forwards LER 79-020/03L-0 | | | 05000338/LER-1979-021-99, /99T-0 on 790212:meterological Air Temp Change in Temp Indication Was Observed to Be off-scale Low.Caused by Faulty Resistance Temp Detector.Temp Element Replaced | /99T-0 on 790212:meterological Air Temp Change in Temp Indication Was Observed to Be off-scale Low.Caused by Faulty Resistance Temp Detector.Temp Element Replaced | | | 05000338/LER-1979-021, Forwards LER 79-021/99T-0 | Forwards LER 79-021/99T-0 | | | 05000338/LER-1979-022-03, /03L-0 on 790227:power Supply to Post DBA H Recombiner Deenergized Rendering Recombiner Inoperable for 4-h.Caused by Deenergizing of Motor Control Center to Perform Voltage Measurements | /03L-0 on 790227:power Supply to Post DBA H Recombiner Deenergized Rendering Recombiner Inoperable for 4-h.Caused by Deenergizing of Motor Control Center to Perform Voltage Measurements | | | 05000338/LER-1979-023, Forwards LER 79-023/03L-0,79-025/03L-0 & 79-031/03L-0 | Forwards LER 79-023/03L-0,79-025/03L-0 & 79-031/03L-0 | | | 05000338/LER-1979-023-03, /03L-0 on 790303:disagreement Noted Between Group & Individual Indication for Rod D-10.Caused by Voltage Drift in Conditioning Card.Calibr & Functional Checks Were Performed | /03L-0 on 790303:disagreement Noted Between Group & Individual Indication for Rod D-10.Caused by Voltage Drift in Conditioning Card.Calibr & Functional Checks Were Performed | | | 05000338/LER-1979-024, Forwards LER 79-024/43X-1 | Forwards LER 79-024/43X-1 | | | 05000338/LER-1979-024-43, /43X-1:on 790228,radwaste Release Occurred Unexpectedly During Pumping of Unit 2 Containment Sump Via Temporary Pump to Storm Drain Sys.Caused by Pressure Relief Valve Leaks in Units 1 & 2 Purge Headers | /43X-1:on 790228,radwaste Release Occurred Unexpectedly During Pumping of Unit 2 Containment Sump Via Temporary Pump to Storm Drain Sys.Caused by Pressure Relief Valve Leaks in Units 1 & 2 Purge Headers | | | 05000338/LER-1979-025-03, /03L-0 on 790228:power Range Channel N42 Placed in Tripped Condition.Caused to Allow Replacement of Erratic Delta Flux Indicator.Indicator Replaced & Power Range Detector Returned to Svc | /03L-0 on 790228:power Range Channel N42 Placed in Tripped Condition.Caused to Allow Replacement of Erratic Delta Flux Indicator.Indicator Replaced & Power Range Detector Returned to Svc | | | 05000338/LER-1979-026-03, /03L-0 on 790306:RHR Discharge Valve Opened Accidentally Causing Loop C Accumulator Level to Drop Below Min Volume Required.Caused by Accidental Operation of MOV-1720B.Valve Closed & Loop Accumulator Level Restored | /03L-0 on 790306:RHR Discharge Valve Opened Accidentally Causing Loop C Accumulator Level to Drop Below Min Volume Required.Caused by Accidental Operation of MOV-1720B.Valve Closed & Loop Accumulator Level Restored | | | 05000338/LER-1979-027-03, /03L-0 on 790225:axial Flux Difference Deviated Greater than 5% from Target.Caused by Xenon Transient Occurring During Startup Operation.Corrected by Boration by Reactor Operator | /03L-0 on 790225:axial Flux Difference Deviated Greater than 5% from Target.Caused by Xenon Transient Occurring During Startup Operation.Corrected by Boration by Reactor Operator | | | 05000338/LER-1979-027, Forwards LER 79-027/03L-0 | Forwards LER 79-027/03L-0 | | | 05000338/LER-1979-028-03, /03L-0 on 790225:greater than 12-step Disagreement Noted Among Rod Position Indication,Computer Position Indication & Demand Signal Indication for Rod 9.Caused by Voltage Drift in Signal Conditioning Card | /03L-0 on 790225:greater than 12-step Disagreement Noted Among Rod Position Indication,Computer Position Indication & Demand Signal Indication for Rod 9.Caused by Voltage Drift in Signal Conditioning Card | | | 05000338/LER-1979-030-03, /03X-1 on 790308:nonconservative Gain Setting on delta-flux Signal Feeding Overpower Delta T Protection Circuitry Observed.Caused by Improper Setting of delta-flux Gain.Signal Recalibr | /03X-1 on 790308:nonconservative Gain Setting on delta-flux Signal Feeding Overpower Delta T Protection Circuitry Observed.Caused by Improper Setting of delta-flux Gain.Signal Recalibr | | | 05000245/LER-1979-030-03, /03L-0 on 790308:calibr Procedure Revealed Nonconservative Gain Setting on delta-flux Signal Feeding Overpower Delta T Protection Circuitry.Caused by Improper Setting of delta-flux Gain.Signal Recalibrated | /03L-0 on 790308:calibr Procedure Revealed Nonconservative Gain Setting on delta-flux Signal Feeding Overpower Delta T Protection Circuitry.Caused by Improper Setting of delta-flux Gain.Signal Recalibrated | | | 05000338/LER-1979-031-03, /03L-0 on 790302:surveillances of Engineered Safety Feature Pumps Not Performed within Interval.Caused by Personnel Error Due to Long Period from Preoperational Tests to Operation.Surveillances Will Be Performed | /03L-0 on 790302:surveillances of Engineered Safety Feature Pumps Not Performed within Interval.Caused by Personnel Error Due to Long Period from Preoperational Tests to Operation.Surveillances Will Be Performed | | | 05000338/LER-1979-032-03, /03L-0 on 790312:containment Vacuum Pump Suction Valve TV-CV150A Would Not Remain Closed When Operated from Control Room.Caused by Relay Sticking in Energized Position.Relay Repaired & Tested Satisfactorily | /03L-0 on 790312:containment Vacuum Pump Suction Valve TV-CV150A Would Not Remain Closed When Operated from Control Room.Caused by Relay Sticking in Energized Position.Relay Repaired & Tested Satisfactorily | | | 05000338/LER-1979-032, Forwards LER 79-032/03L-0 | Forwards LER 79-032/03L-0 | | | 05000338/LER-1979-033, Forwards LER 79-033/03L-0,79-036/03L-0,79-037/03L-0 & 79-038/03L-0 | Forwards LER 79-033/03L-0,79-036/03L-0,79-037/03L-0 & 79-038/03L-0 | | | 05000338/LER-1979-033-03, /03L-0 on 790321: C Steam Generator Narrow Range Level Indicator LI-1496 Gave Readings w/20% Disagreement W/Two Other Channels.Caused by Steam Leak in One Sensing Line Isolation Valve | /03L-0 on 790321: C Steam Generator Narrow Range Level Indicator LI-1496 Gave Readings w/20% Disagreement W/Two Other Channels.Caused by Steam Leak in One Sensing Line Isolation Valve | |
|