Text

March 18, 2020 PG&E Letter DCL-20-017 Justin Rogers Manager Operations Training Diablo Canyon Power Plant P.O. Box 56 Avila Beach, CA 93424 805.545.3088 Internal: 691.3088 Fax: 805.545.4907 Mr. John C. Kirkland, Senior Operations Engineer U.S. Nuclear Regulatory Commission, Region IV 1600 East Lamar Boulevard 10 CFR 55.40 Arlington, TX 76011-4511 Docket No. 50-275, OL-DPR-80 Docket No. 50-323, OL-DPR-82 Diablo Canyon Units 1 and 2 - Initial Operator Licensing Examination: Post-Examination Materials

Dear Mr. Kirkland:

In accordance with the guidance provided in Revision 11 of NUREG-1021, "Operator Licensing Examination Standards for Power Reactors," ES-501, Section C.1.b, Pacific Gas and Electric Company (PG&E) has previously provided the following post-examination materials in electronic or hardcopy format:

Questions & Answers Provided to Applicants Examination Seating Chart Examination Performance Analyses Completed Form ES-201-3, "Examination Security Agreement" Notifications Generated During the Examination In addition to the electronic examination materials, PG&E is submitting the following materials:

  • - ES-403-1, "Written Examination Grading Quality Checklist"

If you have any questions, please contact Mr. Abdul Kadir, Nuclear Examination Development and Simulator Support Supervisor, at 805-545-4200.

A member of the STARS Alliance Callaway

  • Diablo Canyon
  • Palo Verde* Wolf Creek

Mr. John C. Kirkland March 18, 2020 Page2 Sincerely,

~d~

Justin Rogers Operations Training Manager dqmg/6192/5103827 4-28 Enclosures (Post-Examination Materials)

PG&E Letter DCL-20-017 cc:

Matt B. Hayes, Organizational Effectiveness and Learning Services Director Abdul Kadir, Nuclear Examination Development and Simulator Support Supervisor Christopher W. Newport, NRC Senior Resident Inspector James M. Welsch, Senior Vice President, Generation and Chief Nuclear Officer A member of the STARS Alliance Callaway* Diablo Canyon

  • Palo Verde
  • Wolf Creek

L111 Exam Validation 07/30 - 08/02/2012 VALIDATOR R1 R2 R3 R4 R5 R6 S1 S2 S3 S4 S5 S6 S7 S8 AVERAGE Comments: All questions were reviewed with the class with emphasis on questions scoring less than 50%.

Question 09 - Question valid. Knowledge of less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> tech specs. Most knew RWST was covered by LCO did not realize RWST level is a one hour Compeletion Time. Covered LCO with candidates.

Question 40 - Question is valid. Candidates stated they either failed to notice that temperature 542F was given the question or believed that RCS temperature would be stablilized at no load Tave - 547F. This is an action in other EOPs such as E-0.1, Reactor Trip Response but not in E-0. The goal is stablize at current temperature (if less than 547F) to prevent pressurizer overfill. Remediate with candidates.

Question 90 - Question is valid. All that missed it misapplied graphs provided. Remediated with candidates.