The functional issue is limited to N7000 transmitters where the field selectable jumper is set for downscale indication upon loss of input (open circuit, over range
RTD, or short circuit). The transmitter may indicate a mid-range output upon open circuit or over range
RTD input instead of going downscale (4 mA) as intended. Short circuit detection operates correctly in all cases.
This issue does not affect temperature transmitters during normal operating conditions, only the downscale input sensor failure indication function. N7000 transmitters that have been set for upscale sensor failure indication are not affected; however, this notification is applicable to all N7000 customers because the sensor failure indication is field selectable.
The following sites are affected: Oconee, Calvert Cliffs, Perry, North Anna, Surry,
Framatome ANP, Kewaunee, Diablo Canyon, and Hope Creek.