ENS 46824
From kanterella
Revision as of 21:07, 1 March 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
ENS Event | |
---|---|
07:09 May 6, 2011 | |
Title | Discovery of an After-The-Fact Unusual Event |
Event Description | Operators were making preparations to fill the Containment Spray System riser to support outage activities. At 0204 CDT, when Containment Spray Riser Isolation Valve CS-125A was opened, pressurizer level began to lower. The licensee suspects leak by of a valve in the Shutdown Cooling System. At 0214 CDT, the leak was stopped. Pressurizer level was lowered by 2.6%.
After reviewing the event, the licensee determined that the leak rate was greater than 25 gpm which would have resulted in a declaration of an Unusual Event under EAL CU1. Since the event had concluded, no declaration was made. The licensee notified the NRC Resident Inspector. |
Where | |
---|---|
Waterford Louisiana (NRC Region 4) | |
Reporting | |
Other Unspec Reqmnt | |
Time - Person (Reporting Time:+-3.03 h-0.126 days <br />-0.018 weeks <br />-0.00415 months <br />) | |
Opened: | Michael Shumate 04:07 May 6, 2011 |
NRC Officer: | Howie Crouch |
Last Updated: | May 6, 2011 |
46824 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 46824\u003C/a\u003E - \u003Ca href=\"/Waterford\" title=\"Waterford\"\u003EWaterford\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EDiscovery of an After-The-Fact Unusual Event\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 46824 - Waterford\n","link":"","lat":29.993747222222222,"lon":-90.4687111111111,"icon":"/w/images/7/79/Entergy_icon.png"}],"imageoverlays":null} | |
Unit 3 | |
---|---|
Reactor critical | Not Critical |
Scram | No |
Before | Cold Shutdown (0 %) |
After | Cold Shutdown (0 %) |
WEEKMONTHYEARENS 523372016-10-31T16:00:00031 October 2016 16:00:00
[Table view]Other Unspec Reqmnt Supplemental Cooling Inoperable During Movement of Dry Cask Storage Hi-Track Transfer Cask ENS 468242011-05-06T07:09:0006 May 2011 07:09:00 Other Unspec Reqmnt Discovery of an After-The-Fact Unusual Event ENS 406322004-04-01T01:19:0001 April 2004 01:19:00 Other Unspec Reqmnt, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition New Worst Case Single Failure May Exceed 10 Cfr 50.46 Acceptance Criterion for Sbloca ENS 405192004-02-13T11:25:00013 February 2004 11:25:00 Other Unspec Reqmnt 24 Hour Notification Per Licensee Condition 2.F 2016-10-31T16:00:00 | |