The following information was excerpted from report received via email:
The orientation (90 degrees) of the placement (soldering) of the internal wire on the resistor terminal used in the above referenced Series 20 modules may allow the side cover screw to touch the wire insulation. The engineering drawing nor manufacturing assembly instructions did not clearly describe the correct orientation.
On the basis of our evaluation, it was determined on September 30, 2014, that Electroswitch does not have the capability to perform the evaluation to determine if a defect, which could create a substantial safety hazard, exists.
Purchasers are being advised to perform testing to verify operation or return the product to Electroswitch.