TXX-6786, Interim Deficiency Rept CP-87-84 Re Long Electric Cable Leads in Secondary Meter & Relay Current Transformer Circuits Which Could Result in Inoperability of Protective Relays.Initially Reported 870903.Next Rept Submitted 871218

From kanterella
Revision as of 18:10, 8 July 2023 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Interim Deficiency Rept CP-87-84 Re Long Electric Cable Leads in Secondary Meter & Relay Current Transformer Circuits Which Could Result in Inoperability of Protective Relays.Initially Reported 870903.Next Rept Submitted 871218
ML20235R115
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 10/02/1987
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-84, TXX-6786, NUDOCS 8710070795
Download: ML20235R115 (1)


Text

I M

== Log # TXX-6786 i

=-

$ File # 10110 908.3~

=..

1UELECTRIC

" '0" 00'00('}

October 2, 1987 William G. Counsil

_ Eucuene Vice 1%ident _

U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20355

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 DG SECONDARY METER AND RELAY CT CIRCUIT CABLE LEADS SDAR: CP-87-84 (INTERIM REPORT)

Gentlemen:

1 On September 3, 1987, we verbally notified your Mr. H. S. Phillips.of a  !

deficiency involving long electric cable leads in the secondary meter and l relay Current Transformer (CT) circuits for the Emergency Diesel Generator l (DG) which could result in inoperability of the protective relays in the ci rcui t . This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).

ANSI Standard C57.13 requires a percent ratio error not exceeding 10% 'in CT j secondary circuits. Duringthepreparationofcalculation16345-EE(B)-023- l 13G-0, the error for these circuits was found to be 28.57%.

We are continuing our evaluation of the impact of this' issue u)on the-safety l of plant operations. Our next report on this issue will be suamitted not later than December 18, 1987.

Very truly yours, j l

W. G. Counsi1 j WJH:tgj l c- Mr. R. D.' Martin, Region IV Resident Inspectors, CPSES (3) 1' lFoA18ESSkh