Text
I M==
Log # TXX-6786 i
File # 10110
=-
=..
908.3~
'0" 00'00('}
1UELECTRIC October 2, 1987 William G. Counsil
_ Eucuene Vice 1%ident _
U. S. Nuclear Regulatory Commission Attn:
Document Control Desk Washington, D. C. 20355
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)
DOCKET NOS. 50-445 AND 50-446 DG SECONDARY METER AND RELAY CT CIRCUIT CABLE LEADS SDAR: CP-87-84 (INTERIM REPORT)
Gentlemen:
1 On September 3, 1987, we verbally notified your Mr. H. S. Phillips.of a deficiency involving long electric cable leads in the secondary meter and l
relay Current Transformer (CT) circuits for the Emergency Diesel Generator l
(DG) which could result in inoperability of the protective relays in the ci rcui t.
This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).
ANSI Standard C57.13 requires a percent ratio error not exceeding 10% 'in CT j
secondary circuits.
Duringthepreparationofcalculation16345-EE(B)-023-l 13G-0, the error for these circuits was found to be 28.57%.
We are continuing our evaluation of the impact of this' issue u)on the-safety l
of plant operations. Our next report on this issue will be suamitted not later than December 18, 1987.
Very truly yours, j
l j
W. G. Counsi1 WJH:tgj l
c-Mr. R.
D.' Martin, Region IV Resident Inspectors, CPSES (3) 1' lFoA18ESSkh