05000254/FIN-2013003-08
From kanterella
Revision as of 00:19, 22 February 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Finding | |
---|---|
Title | Licensee-Identified Violation |
Description | Title 10 CFR 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings states, in part, that activities affecting quality shall be prescribed by documented drawings and shall be accomplished in accordance with drawings. Electrical Drawing 4E-1461, Schematic Diagram Auto Blow-down Part I, identified the wire in question and indicated that the wire was terminated AA-30. Contrary to the above, the wire was not terminated and previous licensee inspections had not identified the discrepancy. The issue was more than minor because the performance deficiency, if left uncorrected, could be reasonably viewed as a precursor to a more significant event. Specifically, a wire that was not terminated correctly could impair the electrical function of the circuit or the power supply for a required safety function. In this instance, the wire was one of three parallel connections, circuit evaluation indicated that the circuit would perform electrically if this wire had no connectivity, and the wire itself was held in a constrained in a way that would not allow grounding. The wiring for both valves was repaired and operability restored 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and 40 minutes after they were initially declared inoperable. Inspectors answered screening question A.1 of Manual Chapter 0609, Appendix A, Exhibit 2 Yes since no loss of function occurred and the issue screened as Green. |
Site: | Quad Cities |
---|---|
Report | IR 05000254/2013003 Section 4OA7 |
Date counted | Jun 30, 2013 (2013Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | B Cushman C Lipa C Mathews D Szwarc G O'Dwyer J Bozga J Mcghee L Jones R Langstaff S Bell |
Violation of: | 10 CFR 50 Appendix B Criterion V |
INPO aspect | |
' | |
Finding - Quad Cities - IR 05000254/2013003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Quad Cities) @ 2013Q2
Self-Identified List (Quad Cities)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||