05000266/FIN-2006004-02
From kanterella
Revision as of 18:44, 20 February 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Failure to Perform a 50.59 Evaluation of Compensatory Measures Described in Operability Recommendation |
Description | The inspectors identified a Severity Level IV, Non-Cited Violation of 10 CFR 50.59(d)(1) for the licensees failure to perform an evaluation for compensatory actions taken to maintain the closed function of the emergency core cooling system (ECCS) containment sump isolation valves. Specifically, the licensee established compensatory actions in the event remote operation from the control room of the containment sump recirculation isolation valves (1SI-850A, 1SI-850B, 2SI-850A and 2SI-850B) was ineffective during plant minimum or degraded voltage conditions. The licensee had not completed a causal evaluation by the end of the inspection period; however, the remedial corrective actions to address certain aspects of this issue had been implemented. Because violations of 10 CFR 50.59 affect the NRCs ability to perform its regulatory function, this finding was evaluated using the traditional enforcement process. In accordance with the NRC Enforcement Policy, this finding is determined to be more than minor because there was a reasonable likelihood that the change requiring the 10 CFR 50.59 evaluation would require NRC review and approval prior to implementation. This finding has been reviewed by NRC management and is determined to be a Green finding, of very low safety significance. |
Site: | Point Beach |
---|---|
Report | IR 05000266/2006004 Section 1R15 |
Date counted | Jun 30, 2006 (2006Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | R Winter T Ploski J Robbins B Jose G Gibbs J Neurauter M Gryglak M Kunowski L Haeg S Bakhsh R Krsek P Louden |
INPO aspect | |
' | |
Finding - Point Beach - IR 05000266/2006004 | |||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|