, g,* _-
["TS; .n pubuc service company oe conende
- -1 16805 ROAD 19%
1 5 PLATTEVILLE, COLORADO 80651 May 20, 1981 Fort St. Vrain Q h q s
,,\
Unit No. 1 k'>gI"I!I*1 pr"I-
- ,L'9 P-81148 g "', .
- JUN 0 81981 * ~i U S* Ryms .I
~Q g Mr. Karl V. Seyfrit, Director . M.I;Q' Nuclear Regulatory Commission -~
Region IV Office of Inspection and Enforcenent 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76012
Reference:
Facility Operating License No. DPR-34 .
Docket No. 50-267
Dear Mr. Seyfrit:
Enclosed please find a copy of Reportable Occurrence Report No. 50-267/
81-029, Final, submitted per the requirements of Technical Specification AC 7.5.2(b)2.
Also, please find enclosed one copy of the Licensee Event Report for Reportable Occurrence Report No. 50-267/81-029.
Very truly yours,
- ?Y Don Warembourg Manager, Nuclear Production DW/cis Enclosure cc: Director, MIPC 00 )
y
/ /
8106090 e5 6
9 O .*- - .
w REPORT DATE: May 20. 1981 REPORTABLE OCCURRENCE 81-029 ,
ISSUE O OCCURRENCE DATE: Aoril 20. 1981 Page 1 of 3 FORT ST. VRAIN NUCLEAR GENERATING STATION PUBLIC SERVICE COMPANY OF COLORADO 16805 WELD COUNTY ROAD 19 1/2 PLATTEVILLE, COLORADO 80651 i REPORT NO. 50-267/81-029/03-L 0 Final IDENTIFICATION OF '
OCCURRENCE: ,
The 1D emergency diesel of 1B emergency generator set failed the weekly 50% load test. This is raportable per For: S t. Vrain Technical Specification AC 7.5.2(b)2 as a degraded mode of LCO 4.6.ld. [
EVENT DESCRIPTION:
p April 20, 1981 while op-rating at 50% thermal power and 170 W electrical ,
power, the weekly emergency diesel generator 50% load test was conducted. ,
The surveillance for lA emergency generator set was completed satisfactorily. !
The operator secured 1A emergency generator set and started testing on 1B ;
emergency generator set. !
Approximately 10 minutes before the two hour test period was completed, the '
operator checked the 1B emergency generator set and found it operr. Ling properly. About five minutes later, the operator received a call from a ,
security ' guard, who had observed an oil mist in the IB emergency diesel ;
generator room. ;
, The operator returned to the 13 emergency generator room and secured thc.
diesel generator set. Upon examining the diesel engines, he discovered a '
fuel leak on //l injector of 1D diesel engine. ;
Maintenance personnel were called to repair the leaking fuel line and '
found the injector had failed and was jammed in the precombustion chamber.
The entire injector precombustion chamber was removed and replaced. The a emergency diesel generator set was retested and found satisfactory on !
April 23 1981, and'then returned to service.
I CAUSE l
DESCRIPTod: ,
The cause of this occurrence was a failed fuel injector. )
l 1
. j t
1
r:
. , , i? s'a_ ~
A REPORTABLE OCCURRENCE 81-029 ISSUE O Page 2 of 3 CORRECTIVE ACTICN:
The fuel injector and precombustion chamber were replaced. The emergency generator set was retested and returned to service.
No further corrective action is anticipated or required.
l I
1
?
b j$h e-mew . - , y+ y .,--,,-.,,94--9 --, --y , y y---f --ap- y- , . -r- g -w-+-*
.,.....?_ .
REPORTABLE OCCURRENCE 81-029 ISSUE 0 Page 3 of 3 I Prepared By:
f
( 2/A. ,
i Asa B. Reed Technical Services Technician i
t i
Reviewed By:
l
/e.T W/Gahm chnical Services Supervisor i
Reviewed By:
Frank M. Mathie Operations Manager Approved By: Ne n . . M Don Warembourg Manager, Nuclear Produ/
ction l
l l
, . , _ , , _ , _ . . . _ , . . . . , _ . _ . . - _