THE-CLEVELAND ELECTRIC ILLUMINATING COMPANY P.O. BOX 97 5 PERRY, OHIO 44001 - B TELEPHONE (216) 259 3737. B ADDRESS 10 CENTER ROAD ~
FROM CLEVELAND: 4 4 1260 .B TELEX: 241500 AN8WERBACK: CEIPRYO l
Al Kaplan Serving The Best location in the Nation i PERRY NUCLEAR POWER PLANT VICE PRESIDENT NUCdAR GHOUP January 9, 1990 PT-CEI/NRR-1118 L U.S. Nuclear Regulatory Commission Document Control Desk Washington, D. C. 20555 Perry Nuclear Power Plant Docket No. 50-440 .
I Request for Additional'Information.-
NRC Bulletin 88-04 (TAC No.J69954)- i Gentlemen:
i Our letter PY-CEI/NRR-1081L dated December' 13, 1989 provided the following' (
information on RCIC pump minimum flow limitations from PNPP operating -j instructions, however, the inequality signs were. inadvertently _omitted ..;
" Maintain the RCIC Pump flow greater than or equal..to the following-limitations: .I
'30 minutes- 10' minutes RPM Continuous Duty in 24' hour ~ period in 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period , :i
< 2250 140 GPM 85 GPM .NA 7 2250 345 GPM 225 GPM 120 GPM NOTE: RCIC MIN FLOW VALVE, 1E51-F019, passes .120 GPM'.' l The RCIC pump manufacturer has confirmed that operation of the system'within {
the limits of this table will not result in pump degradation. 'If you have any 1 questions, please, feel free to call. '
Very truly 8,.
Al Kaplan Vice President-Nuclear Group ;
AK:nje cc: T. Colburn P. Hiland '
USNRC, Region III h 7 g.
1 9001170408.900109 7 /