Text
,. . ,. ,=
0Go Back Print I New Search I Home AR 01319908 Report Aff Fac: Byron AR Type: CR Status: APPROVED Aff Unit: 02 Owed To: ACAPALL Due Date: 02/29/2012 Aff System: SY Event Date: 01/30/2012 CR 2/A Disc Date: 01/30/2012 LevellClass:
How H01 Orig Date: 01/30/2012 Discovered:
WR/PIMS Equip Tag:
AR:
Action Request Details
Subject:
U2 REACTOR TRIP DUE TO ELECTRICAL FAULT AND UNUSUAL EVENT (b)(6) (b)(6)
Description:
Originator: I Supv Contacted:
Condition
Description:
At 1002 U2 reactor tripped due to an aparent electrical fault. A loss of offsIte power followed. 2A and 2B Diesel generators energized the ESF buses. U2 SAT was Isolated based on reports of smoke. Investigation shows a failure of C Phase at the SAT disconnect.
Immediate actions taken:
Enteed 2BEP 0. The Main steam isolation valves were closed. Initiated actions per the BEPs.
Recommended Actions:
Perform a root cause. Subsequent IR's will be written for repairs.
Operable Basis:
Reportable Basis:
Functionality Basis:
(b)(6)
SOC Reviewed by: 01/30/2012 16:28:00 CST SOC Comments:
Send to Ops to generate root cause actions. Level 2 event due to plant trip per LS-AA-120. ZINWR 1/30/12 Assignments Assign #: 01 Assigned Status: AWAIT/C To:
M itnthe Freedm ofd n md
= d~~ *lth the Freedom of lnb *JM, C_2_
Aff Fac: Byron Prim Grp: ACAPALL Due Date: 02/04/2012 Assign Type: TRKG Sec Grp: Orig Due Date:
Priority:
Schedule Ref:
Unit Condition:
Subject/Description: U2 REACTOR TRIP DUE TO ELECTRICAL FAULT AND UNUSUAL EVENT