05000335/FIN-2009004-03
From kanterella
Revision as of 19:40, 28 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Failure to take timely and effective corrective actions to prevent recurrence of EDG Day Tank level switch failures. |
Description | A self-revealing Non-Cited Violation (NCV) of 10 CFR 50, Appendix B, Criterion XVI, Corrective Action, was identified for failure of the licensee to take timely and effective corrective actions to prevent recurrence of Unit 1 emergency diesel generator (EDG) day tank level switch failures following identification of Murphy switch reliability issues and issuance of NRC NCV 05000335/2009002-02. Specifically, on July 19, 2009, during functional testing of the 1B EDG day tank level switches, both the low and low-low level Murphy switches failed. The finding is more than minor because it is associated with the equipment performance attribute of the mitigating systems cornerstone. The finding was previously determined to have very low safety significance based on an SDP Phase 3 analysis. The analysis determined that the risk was less than 1E-6/year. This finding was related to the corrective action attribute of the problem identification and resolution cross-cutting area in the aspect of appropriate and timely corrective actions (IMC 0305 aspect P.1.d). (Section 4OA2.3 |
Site: | Saint Lucie |
---|---|
Report | IR 05000335/2009004 Section 4OA2 |
Date counted | Sep 30, 2009 (2009Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | A Vargas J Sowa M Sykes N Smith R Chou S Sanchez T Hoeg T Morrissey T Ross |
Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion XVI |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |
Finding - Saint Lucie - IR 05000335/2009004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Saint Lucie) @ 2009Q3
Self-Identified List (Saint Lucie)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||