 Entered dateEvent description
ENS 5173012 February 2016 03:51:00On 02/11/2016, at 2305 (EST), Ginna Station experienced a loss of Station Service Transformer 12A causing Emergency Diesel Generator 1A to automatically start due to under-voltage signals to safeguards buses 14 and 18. All plant systems responded as designed. Control room operators stabilized the plant per abnormal operating procedures. The plant is currently in a 100/0 electrical lineup (supplied by the 12B Service Station Transformer) on the off site circuit 767 with the 1A Emergency Diesel Generator secured. The loss of the station service transformer is currently under investigation. This is reportable as a valid system actuation that was not part of a pre-planned sequence during testing. The NRC Resident Inspector has been notified.