 Entered dateEvent description
ENS 5403126 April 2019 20:19:00At 1147 (CDT) on 4/26/19, a through wall leak (reported as 1 drop every 1 to 2 minutes) was identified and confirmed by operation and NDE (Non-Destructive Examination) personnel on the Standby Liquid Control injection line during pressure testing activities. The line is 1.5 inch in diameter and classified as an ASME Section Ill, Class 1 line. The leak is currently isolated from the reactor vessel by a danger tagged manual valve. The licensee notified the NRC Resident Inspector.