Semantic search

Jump to navigation Jump to search
Condition
Printout selection
Options
Parameters [
limit:

The maximum number of results to return
offset:

The offset of the first result
link:

Show values as links
headers:

Display the headers/property names
mainlabel:

The label to give to the main page name
intro:

The text to display before the query results, if there are any
outro:

The text to display after the query results, if there are any
searchlabel:

Text for continuing the search
default:

The text to display if there are no query results
class:

An additional CSS class to set for the table
transpose:

Display table headers vertically and results horizontally
sep:

The separator between results
prefix:

Control display of namespace in printouts
Sort options
Delete
Add sorting condition
 Entered dateEvent description
ENS 4176110 June 2005 09:07:00Ametek Solid State Controls produces AC-DC power supplies that are used at several nuclear power plants. Ametek states that its Series AC-DC power supplies may have a problem with premature failure. The specific Model Numbers affected are as follows: 85-RP1510-00 85-RP4804-00 85-RP4808-00 85-RP DUAL-4807\1 Ametek states that an intermittent loss of continuity in a magnet wire connector may cause overheating in a lug and transformer which could eventually result in a premature failure of the power supply ( within approximately two years of initial service). The problem was discovered during testing of a power supplies by Ametek. No nuclear power plants have reported any problems with the power supplies. Ametek states that its records indicate that these power supplies were supplied to Braidwood, Byron, and DC Cook. Ametek believes that the power supplies are used for control rod instrumentation. A total of 33 power supplies have been sold but Ametek believes that most of these are not in service. Ametek recommends that these power supplies either be returned to Ametek for rework or that the affected sites request a service by an Ametek representative onsite.