TXX-4966, Final Deficiency Rept CP-86-34 Re Fire Stop Installations Exceeding Design Temp of Unexposed Surface During ASTM E-119 Fire Test.Initially Reported on 860501.Issue Not Reportable Under 10CFR50.55(e)
| ML20212P677 | |
| Person / Time | |
|---|---|
| Site: | Comanche Peak |
| Issue date: | 08/22/1986 |
| From: | Counsil W, Keeley G TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC) |
| To: | Johnson E NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
| References | |
| CP-86-34, TXX-4966, NUDOCS 8609030232 | |
| Download: ML20212P677 (1) | |
Text
'
Log # TXX-4966 File # 10110 909.5 TEXAS UTILITIES GENERATING COMPANY fsKYWAY TOWER . 400 NORTH OLIVE FrREET. L.B. 81. DALLAS. TEXAS 75301 August 22, 1986 23"Et??Jft.S % g @ g []W M %
)r- l AUG 2 71986 Mr. Eric H. Johnson, Director Division of Reactor Safety and Projects _
O U. S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76012
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)
DOCKET NOS. 50-445 AND 50-446 DEFECTIVE FIRE STOP INSTALLATIONS SDAR: CP-86-34 (FINAL REPORT)
Dear Mr. Johnson:
On May 1,1986, we verbally notified your Mr. T. F. Westerman of a deficiency where we may have exceeded the design temperature of the unexposed surface for several fire seal designs during an ASTM E-119 fire test. We have submitted interim reports logged TXX-4834 and TXX-4881, dated May 30, 1986, and June 27, 1986, respectively. We received an extension from your Mr. T. Westerman until August 22, 1986.
Evaluation of the test data shows that the seal in question was tested in accordance with ASTM E-119 criteria and was found to be acceptable.
Furthermore, the fire protection design matrix has been upgraded by the fire seal supplier (BISCO). A new fire test was added to further verify that the fire seal in question was acceptable. Therefore, we have concluded that this specific issue is not reportable under the provisions of 10CFR50.55(e).
Records supporting this determination are available for your inspectors to review at the CPSES site.
Very truly yours, h hil W. G. Counsil 8609030232 ADOCK h43 By: - e d PDR PDR G.S. Keeley o /_
S Manager,Nucleargtensing 4
- JCH/amb h