05000416/FIN-2008002-05
From kanterella
Revision as of 20:35, 28 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Finding | |
---|---|
Title | Failure To Evaluate Cracks In Standby Service Water Pump House Structure |
Description | The inspectors identified a Green noncited violation of 10 CFR Part 50 Appendix B, Criterion XVI, for failing to implement effective corrective actions after identifying concrete cracking in the standby service water pump houses. The inspectors determined that the program that evaluates, monitors, and repairs cracks for all safety related structures only identified a single crack for the entire site and does not track other structural cracks previously identified in the corrective action program. The last program inspection had been performed as recently as October 25, 2007, and only identified the single crack that had been documented in previous inspections. This issue was entered into the licensees corrective action program as Condition Report CR-GGN-2007-05824. This finding was more than minor because the cracks represent a degrading condition that if left uncorrected could become a more significant safety concern. The inspectors determined this finding affected the mitigating systems cornerstone. Using the Manual Chapter 0609, Significance Determination Process, Phase 1 worksheet, this finding was of very low safety significance since it did not represent an actual loss of a safety function. The cause of this finding has a crosscutting aspect in the area of human performance associated with work practices because the licensee personnel failed to properly maintain and utilize the program for evaluating, tracking and repairing identified concrete cracks in safety related structures H.4(b) (Section 4OA2) |
Site: | Grand Gulf |
---|---|
Report | IR 05000416/2008002 Section 4OA2 |
Date counted | Mar 31, 2008 (2008Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | R Deese P Elkmann R Smith A Barrett D Bollock |
CCA | H.8, Procedure Adherence |
INPO aspect | WP.4 |
' | |
Finding - Grand Gulf - IR 05000416/2008002 | |||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Grand Gulf) @ 2008Q1
Self-Identified List (Grand Gulf)
| |||||||||||||||||||||||||||||||||||||||||||||||||