- 05000416/LER-1983-109, Updated LER 83-109/03X-2:on 830727,spurious RHR Room High Area Temp or Delta Temp Signal Caused Inboard Shutdown Cooling Valve F009 Closure.Caused by Loose Plug Connection on Riley Temp switch.W/840214 Ltr (← links)
- 05000416/LER-1983-177, Updated LER 83-177/03X-1:on 831029,1102 & 06,water Collected in Offgas Pretreatment Monitor,Resulting in Improper Flow Through Monitor.Caused by Accumulation of Condensation.Heat Tracing Installed on piping.W/840213 Ltr (← links)
- 05000416/LER-1983-189, Updated LER 83-189/03X-1:on 831207 & 840201,breaker 152-1704 to Div 3 ESF Bus Tripped.Caused by Broken Current Limiter Resistor Socket for Breaker Position Indicating Light. Agastat Relay 7012 Replaced (← links)
- 05000416/LER-1983-037, Forwards LER 83-037/03L-0 (← links)
- 05000416/LER-1983-030, Forwards LER 83-030/99X-0 (← links)
- 05000416/LER-1983-009, Forwards LER 83-009/03L-0 (← links)
- 05000416/LER-1983-002, Forwards LER 83-002/01T-0 (← links)
- 05000416/LER-1983-004, Forwards LER 83-004/01T-0 (← links)
- 05000416/LER-1983-128, Updated LER 83-128/01X-1:on 830912 During Routine Maint,Two fire-rated Penetrations Found Unsealed.Caused by Procedural Inadequacy.Penetrations Resealed (← links)
- 05000416/LER-1983-115, Updated LER 83-115/03X-1:on 830803 & 04,RHR Pump a Failed to Start.Div I Busses Incorrectly Shown Tripped,Annunciator Panels Came On,Optical Isolator Failed & Breakers Tripped. Caused by Incorrectly Terminated Cable (← links)
- 05000416/LER-1983-011, Updated LER 83-011/99X-2:on 830103-24,fire-rated Barriers in Control & Auxiliary Bldgs Opened to Perform Planned Maint.Fire Watches Established.All Fire Barriers Restored (← links)
- ML20079P446 (redirect page) (← links)
- 05000416/LER-1983-042 (redirect page) (← links)
- 05000416/LER-1983-041, Forwards LER 83-041/03L-0 (← links)
- 05000416/LER-1983-044, Forwards LER 83-044/99X-0 (← links)
- 05000416/LER-1983-032, Forwards LER 83-032/03L-0 (← links)
- 05000416/LER-1983-034, Forwards LER 83-034/03L-0 (← links)
- 05000416/LER-1983-040, Forwards LER 83-040/03L-0 (← links)
- 05000416/LER-1983-039, Forwards LER 83-039/99X-0 (← links)
- 05000416/LER-1983-021, Updated LER 83-021/01T-1:on 830519,determined That Standby Gas Treatment Sys Flow Monitoring Instrumentation Reading in Error.Caused by Incorrect Calibr Range Based on Postulated Instead of Std Conditions.Instruments Recalibr (← links)
- 05000416/LER-1983-051, Forwards LER 83-051/03L-0 (← links)
- 05000416/LER-1983-058, Forwards LER 83-058/01T-0 (← links)
- 05000416/LER-1983-063, Forwards LER 83-063/01T-0 (← links)
- 05000416/LER-1983-067, Forwards LER 83-067/01T-0 (← links)
- 05000416/LER-1983-059, Forwards LER 83-059/03L-0 (← links)
- 05000416/LER-1983-043, Forwards LER 83-043/03L-0 (← links)
- 05000416/LER-1983-045, Forwards LER 83-045/99X-0 (← links)