- BSEP-82-2928, RO 1-82-154:on 821222,review Revealed Mode 5 Entered W/O Meeting Tech Spec Requirements.Average Power Range Monitors & Bldg Ventilation Radiation Monitors Not Verified Operational.Mode Switch Not Locked in Refuel Position (← links)
- BSEP-83-2234, Ro:On 830601,gamma Analysis of Two Bottom Sediment Samples Detected Excessive Co-60 Concentration at Sample Stations 33 & 34.No Radiation Hazard or Exposure to Public.Sampling Frequency Increased (← links)
- BSEP-83-3042, RO I-83-01:on 830811,HPCI Sys Declared Inoperable Due to Problems Found During Operability Test.Ler Will Be Submitted by 830930 (← links)
- BSEP-83-3006, RO 1-83-40:on 830904,while Performing Periodic Test A4 on RCIC Steam Line High D/P Instrumentation,Hpci & RCIC Isolated.Caused by Periodic Test Incorrectly Written. Results Will Be Reported in 14-day Rept (← links)
- BSEP-83-2747, RO 2-SR-83-22:on 830705,gamma Analysis of Two Botton Sediment Samples Detected Excessive Co-60 Concentration. No Radiation Hazard or Exposure to Public.Sampling Frequency Increased from Semiannual to Monthly (← links)
- BSEP-83-2733, RO 1-83-34:on 830812,isolation Valves from Drywell That Isolate Reactor Bldg to Suppression Chamber Vacuum Breaker Differential Pressure Switches Closed,Rendering Both Breakers Inoperable.Investigation in Progress (← links)
- BSEP-83-1618, Ro:On 830509,main Condenser Steam Jet Air Ejector Offgas Radiation Monitors a & B Failed to Indicate Power Level. Caused by Closure of Root Isolation Valves to Each Monitor. Shift Personnel Counseled (← links)
- BSEP-83-2702, Ro:On 830730,during Planned Release of Floor Drain Sample Tank A,Determined That Radiological Liquid Waste Effluent Recorder Not Indicating Release Flow Rate.Caused by Blown Protective Fuse (← links)
- BSEP-83-1421, Ro:On 830404,fire Barrier Limiting Conditions for Operation Initiated on Penetration Seal CB-2-301 of Fire Door 221. Caused by Need to Allow Ambient Air Circulation Due to Inoperability of Computer Room Air Conditioner (← links)
- BSEP-83-1236, Ro:Fire Barrier Limiting Conditions for Operation Issued on 830317 & 20 Exceeded 7-day Time Frame to Permit Completion of Mods in Control,Diesel Generator & Augmented Offgas Bldgs.Continuous Stationed Fire Watches Maintained (← links)
- BSEP-83-1240, RO:7-day Specified Time Frame of Four Fire Barrier Limiting Conditions for Operation Exceeded,To Permit Work in Augmented Offgas & Control Bldgs for Installation of Two Plant Mods.Fire Watches Will Remain in Effect (← links)
- BSEP-83-1202, Nonroutine Radiological Environ Event Rept.Results of 830308 Gamma Analysis of Bottom Sediment Revealed High Co-60 Concentration.Samples Will Be Taken Monthly for Oct 1982 - June 1983 to Determine If Trends Can Be Predicted (← links)
- BSEP-83-1150, Ro:On 830408,during Refueling Outage,Seven Day Time Frame of Four Fire Barrier Limiting Conditions for Operation Exceeded.Caused by Complicated Mods.Fire Watches Will Continue Until Work Completed (← links)
- BSEP-83-1151, Ro:On 830302,four Fire Barrier Limiting Conditions for Operation Generated to Permit Work in Svc Water Bldg for Installation of Plant Mod.Seven Day Time Limit Exceeded. Plant Mod Completed on 830404 (← links)
- BSEP-83-1146, Ro:On 830302,control Bldg Fire Door CB-205 Found Inoperable Due to Problem W/Automatic self-closer.Repairs Unsatisfactory.Repair Time Frame Exceeded.Work Request Forms to Be Tracked on Immediate Action List (← links)
- BSEP-91-0177, Special Rept 1-SR-91-001:on 910326,limiting Conditions for Operation Initiated Due to Inoperable Fire Doors.Caused by Routine Usage.Fire Doors 207,107 & 214 Repaired & Restored on 910402.Station Fire Watches Were Maintained (← links)
- BSEP-83-1102, Ro:On 830221,fire Barrier Penetration Limiting Conditions for Operation 1-83-115 Issued to Permit Work on 20-ft Elevation of Svc Water Bldg Required for Installation of Plant Mod.Due to Work complexity,7-day Time Frame Exceeded (← links)
- BSEP-83-1122, RO 2-83-43:on 830405,required Actions for Inoperable Fire Barriers in Augmented Gas Bldg Not Taken During Evaluation of Fire Protection Limiting Conditions.Continuous Fire Watches Established (← links)
- BSEP-83-1116, Ro:On 830228,post-maint Testing of Fire Door 103 Revealed High Differential Air Pressure Across Door.Fire Watch Will Be in Effect Until Door Operable (← links)
- BSEP-83-1083, Ro:During Refueling Outage,Fire Barrier Limiting Conditions for Operation 1-82-110 Generated to Permit Installation of Mod on Svc Water Sys Screen Pump 1A.Due to Complexity of work,7-day Time Frame Exceeded (← links)
- BSEP-83-1979, Ro:On 830504,during Shutdown Operations,Limiting Conditions for Operations (LCO) Initiated for Inoperable Fire Door 203. Caused by Door Misalignment.Due to Job Planning considerations,7-day Time Frame of LCO Exceeded (← links)
- BSEP-83-1800, Ro:On 830502,gamma Analysis of Bottom Sediment Sample Detected Excessive Co-60 Activity.Sampling Frequency Increased from Semiannually to Monthly.Sample Represents Seventh Monthly Sample (← links)
- BSEP-83-1882, Ro:On 830513,limiting Condition for Operation Initiated for Fire Door 213 in Diesel Generator Bldg.Door Encountered High Differential Air Pressure Across Door Preventing self- Closure.Engineering Evaluating Pressure Problem (← links)
- BSEP-83-1875, Ro:On 830513,limiting Condition of Operation Initiated for Fire Door 202 in Diesel Generator Bldg.Door Inoperable Due to High Differential Air Pressure Encountered Across Door Preventing self-closure (← links)
- BSEP-83-1770, Ro:On 830504,limiting Condition for Operation Initiated for Inoperable Fire Door 208 on 49-ft Elevation of Control Bldg.Caused by Misaligment of Door within Door Frame.Door to Be Repaired Upon Receipt of Parts (← links)
- BSEP-83-1769, Ro:On 830512 & 19,Fire Doors 106,109 & 201 Declared Inoperable Due to High Differential Air Pressure Across Each Door Preventing Automatic self-closure.Evaluation of Air Pressure Problem Underway (← links)
- BSEP-83-1728, Ro:On 830521,during Power Operation,Electrical Panels HB5 & HB8 Discovered Deenergized.Basic Ground Rules by Which Test & Const Personnel May Operate Equipment Not Well Understood at Time of Discovery (← links)
- BSEP-83-1669, Ro:On 830426,fire Barrier Limiting Condition for Operation Initiated for Augmented Offgas Bldg Door.Mod Time Frame Exceeded 7-day Specified Period.Fire Watches Will Remain in Effect (← links)
- BSEP-83-1581, Ro:Increased Co-60 Activity Found in Two Bottom Sediment Samples Collected 830405 & 06.No Co-60 Found in Surface Water Samples from Intake & Discharge Canals During Apr 1983.No Radiation Hazard or Exposure to Public Observed (← links)
- BSEP-83-1716, Suppl to Special RO Rept:On 830509,main Condenser Steam Jet Air Ejector Offgas Radiation Monitors a & B Found Not Indicating as Expected for 2,330 Power Level.Caused by Closure of Root Isolation Valves (← links)
- BSEP-82-2145, Ro:On 821001,analysis Confirmed That Pipe Support PS-6647 Could Fail During Seismic Event.Support Upgraded to Meet Requirements (← links)
- BSEP-82-2906, RO 1-82-154:on 821214,while Detensioning Reactor Vessel Head,Operational Mode 5 Entered W/O Meeting Tech Spec 3.0.4 Requirements.Investigation Underway & Mode 5 Requirements Under Review (← links)
- BSEP-82-2883, RO 2-82-139:on 821216,reactor Water Cleanup Sys High Differential Flow Isolation Instrumentation Declared Inoperable Due to Erratic Flow Transmitter.Caused by Personnel Error.Instrumentation Repaired & Restored to Svc (← links)
- BSEP-82-2811, Ro:On 821209,while Performing Corrective Maint on Main Steam Line High Flow Isolation Instrument,Group I Isolation Signal Mistakenly Reset.Placement of Jumpers in Control Logic Allowed Resetting of Isolation.Signal Reinserted (← links)
- BSEP-82-2597, RO 2-82-124:on 821121,while Performing Monthly Operability Test on Diesel Generator 3,required 2-h Quick Starts for Remaining Three Diesel Generators Not Performed.Caused by Misinterpretation of Adminstrative Controls (← links)
- BSEP-91-0020, Special Rept 1-SR-90-005:on 901130,Zone 1 of Svc Water Bldg Fire Detection Sys Declared Inoperable Due to Spurious Alarms on Main Control Room Annunicator.Caused by Defective Pull Station.Fire Detection Panel Replaced (← links)
- BSEP-82-2403, RO 2-82-130:on 821029,during Routine Insp of Drywell,Crack Found on RHR Shutdown Cooling Suction Line.Sample of Defect Being Sent to Harris Meteorological Lab.Defect Will Be Welded by 821103 (← links)
- BSEP-90-0827, Special Rept 1-SR-90-004:on 901121,7-day Time Frame of LCO Exceeded.Caused by Fire Barrier Penetration Seal Out of Svc for Inservice Insp Work.Until Work Completed,Hourly Fire Watch Patrol Will Remain in Effect (← links)
- BSEP-82-2259, Ro:While Performing Insp of Fire Dampers Per 820518 Commitment,Discovered Ventilation Duct Located at Penetration Seal DG-2-034 on 23-ft Elevation of Diesel Generator Bldg Did Not Have Insp Door (← links)
- BSEP-90-0799, Special Rept 1-SR-90-003:on 901016,reactor Bldg Fire Detection Sys Zone 14 Instrumentation Declared Inoperable. Hourly Fire Watch Patrol in Effect (← links)
- BSEP-94-0103, Special Rept 1-SR-94-002:on 940226,fire Barrier Penetration Between EDG Bldg & Diesel Fuel Oil Day Storage Tank Room Opened.Fire Watch Stationed Prior to Opening Penetration & Remained in Place Until Penetration Fire Seal Operable (← links)
- BSEP-82-1753, RO 2-82-84:on 820811,two Dampers in Control Bldg Ventilation Sys Failed to Receive Close Signal Upon Detection of Chlorine.Mod Will Be Installed Prior to Unit Startup (← links)
- BSEP-90-0782, Special Rept 1-SR-90-002:on 901028,7-day Time Frame of LCO Exceeded for Fire Door 203.Fire Watches Remained Stationed Until LCO Canceled on 901029 (← links)
- BSEP-93-0238, Special Rept SR 1-93-013:on 931117,fire Protection LCO A1-93-F0859 Initiated on Fire Seal R1-2-077.Seal Inoperable to Facilitate Overspeed Trip Setting Testing of HPCI & RCIC Sys.Fire Seal Restored on 931204 (← links)