| Line 1: |
Line 1: |
| {{Adams
| | #REDIRECT [[05000267/LER-1981-029, Forwards LER 81-029/03L-0.Detailed Event Analysis Encl]] |
| | number = ML20004D669
| |
| | issue date = 05/20/1981
| |
| | title = Forwards LER 81-029/03L-0.Detailed Event Analysis Encl
| |
| | author name = Gahm J, Reed A, Warembourg C, Warembourg D
| |
| | author affiliation = PUBLIC SERVICE CO. OF COLORADO
| |
| | addressee name = Seyfrit K
| |
| | addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
| |
| | docket = 05000267
| |
| | license number =
| |
| | contact person =
| |
| | document report number = P-81148, NUDOCS 8106090635
| |
| | package number = ML20004D670
| |
| | document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE, UTILITY TO NRC
| |
| | page count = 4
| |
| }}
| |
| | |
| =Text=
| |
| {{#Wiki_filter:, g,* _-
| |
| ["TS; .n pubuc service company oe conende
| |
| #-1 16805 ROAD 19%
| |
| 1 5 PLATTEVILLE, COLORADO 80651 May 20, 1981 Fort St. Vrain Q h q s
| |
| ,,\
| |
| Unit No. 1 k'>gI"I!I*1 pr"I-
| |
| - ,L'9 P-81148 g "', .
| |
| ; JUN 0 81981 * ~i U S* Ryms .I
| |
| ~Q g Mr. Karl V. Seyfrit, Director . M.I;Q' Nuclear Regulatory Commission -~
| |
| Region IV Office of Inspection and Enforcenent 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76012
| |
| | |
| ==Reference:==
| |
| Facility Operating License No. DPR-34 .
| |
| Docket No. 50-267
| |
| | |
| ==Dear Mr. Seyfrit:==
| |
| | |
| Enclosed please find a copy of Reportable Occurrence Report No. 50-267/
| |
| 81-029, Final, submitted per the requirements of Technical Specification AC 7.5.2(b)2.
| |
| Also, please find enclosed one copy of the Licensee Event Report for Reportable Occurrence Report No. 50-267/81-029.
| |
| Very truly yours,
| |
| - ?Y Don Warembourg Manager, Nuclear Production DW/cis Enclosure cc: Director, MIPC 00 )
| |
| y
| |
| / /
| |
| 8106090 e5 6
| |
| | |
| 9 O .*- - .
| |
| w REPORT DATE: May 20. 1981 REPORTABLE OCCURRENCE 81-029 ,
| |
| ISSUE O OCCURRENCE DATE: Aoril 20. 1981 Page 1 of 3 FORT ST. VRAIN NUCLEAR GENERATING STATION PUBLIC SERVICE COMPANY OF COLORADO 16805 WELD COUNTY ROAD 19 1/2 PLATTEVILLE, COLORADO 80651 i REPORT NO. 50-267/81-029/03-L 0 Final IDENTIFICATION OF '
| |
| OCCURRENCE: ,
| |
| The 1D emergency diesel of 1B emergency generator set failed the weekly 50% load test. This is raportable per For: S t. Vrain Technical Specification AC 7.5.2(b)2 as a degraded mode of LCO 4.6.ld. [
| |
| EVENT DESCRIPTION:
| |
| p April 20, 1981 while op-rating at 50% thermal power and 170 W electrical ,
| |
| power, the weekly emergency diesel generator 50% load test was conducted. ,
| |
| The surveillance for lA emergency generator set was completed satisfactorily. !
| |
| The operator secured 1A emergency generator set and started testing on 1B ;
| |
| emergency generator set. !
| |
| Approximately 10 minutes before the two hour test period was completed, the '
| |
| operator checked the 1B emergency generator set and found it operr. Ling properly. About five minutes later, the operator received a call from a ,
| |
| security ' guard, who had observed an oil mist in the IB emergency diesel ;
| |
| generator room. ;
| |
| , The operator returned to the 13 emergency generator room and secured thc.
| |
| diesel generator set. Upon examining the diesel engines, he discovered a '
| |
| fuel leak on //l injector of 1D diesel engine. ;
| |
| Maintenance personnel were called to repair the leaking fuel line and '
| |
| found the injector had failed and was jammed in the precombustion chamber.
| |
| The entire injector precombustion chamber was removed and replaced. The a emergency diesel generator set was retested and found satisfactory on !
| |
| April 23 1981, and'then returned to service.
| |
| I CAUSE l
| |
| DESCRIPTod: ,
| |
| The cause of this occurrence was a failed fuel injector. )
| |
| l 1
| |
| . j t
| |
| 1
| |
| | |
| r:
| |
| . , , i? s'a_ ~
| |
| A REPORTABLE OCCURRENCE 81-029 ISSUE O Page 2 of 3 CORRECTIVE ACTICN:
| |
| The fuel injector and precombustion chamber were replaced. The emergency generator set was retested and returned to service.
| |
| No further corrective action is anticipated or required.
| |
| l I
| |
| 1
| |
| ?
| |
| b j$h e-mew . - , y+ y .,--,,-.,,94--9 --, --y , y y---f --ap- y- , . -r- g -w-+-*
| |
| | |
| .,.....?_ .
| |
| REPORTABLE OCCURRENCE 81-029 ISSUE 0 Page 3 of 3 I Prepared By:
| |
| f
| |
| ( 2/A. ,
| |
| i Asa B. Reed Technical Services Technician i
| |
| t i
| |
| Reviewed By:
| |
| l
| |
| /e.T W/Gahm chnical Services Supervisor i
| |
| Reviewed By:
| |
| Frank M. Mathie Operations Manager Approved By: Ne n . . M Don Warembourg Manager, Nuclear Produ/
| |
| ction l
| |
| l l
| |
| , . , _ , , _ , _ . . . _ , . . . . , _ . _ . . - _}}
| |