ML20040C945: Difference between revisions

From kanterella
Jump to navigation Jump to search
StriderTol Bot insert
 
StriderTol Bot change
 
Line 1: Line 1:
{{Adams
#REDIRECT [[05000311/LER-1981-130, Forwards LER 81-130/03L-0.Detailed Event Analysis Encl]]
| number = ML20040C945
| issue date = 01/15/1982
| title = Forwards LER 81-130/03L-0.Detailed Event Analysis Encl
| author name = Midura H
| author affiliation = PUBLIC SERVICE ELECTRIC & GAS CO. OF NEW JERSEY
| addressee name = Haynes R
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
| docket = 05000311
| license number =
| contact person =
| document report number = NUDOCS 8201290398
| package number = ML20040C946
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE, UTILITY TO NRC
| page count = 3
}}
 
=Text=
{{#Wiki_filter:'
O PSEG Put> tic Service Electric and Gas Company P.O. Box 168 Hancocks Bridge, New Jersev 08038 Salem Generating Station January 15, 1982 Mr. R. C. Ilaynes                                                                      m
                                                                                            ~
Director of USNRC                                                              T-        s Office of Inspection and Enforcement                                                            ,
Region 1                                                                  @                  (a 631 Park Avenue                                                                  RECElygo King of Prussia, Pennsylvania                      19406                      Mgg                [
6}
 
==Dear Mr. Ilaynes :==
                                                      'k-9,\
fNhf]pgM U ice      q LICENSE NO. DPR-75                                                              ,
DOCKET NO. 50-311                                                              N/        f REPORTABLE OCCURRENCE 81-130/03L Pursuant to the requirements of Salem Generating Station Unit No. 2, Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 81-130/03L. This report is required within thirty (30) days of the occurrence.
Sincerely yours, l        ]lffltrw' H. J. Midura General Manager -
Salem Operations FD:      al Distribution QCC:
8201290398 820115 Th e E. e r g'y' P t'                                                                          ,sm nn, , n y hDRADOCK05000 b
 
  .                    .  .    .                  . m
      . .                                                                  e
          ?eport Number:    81-130/03L Report Date:      01-15-82 Occurrence Date:  12-19-81 and 12-21-81 Facility:          Salem Generating Station, Unit 2 Public Service Electric & Gas Company H acocks Bridge, New Jersey    08038 IDENTIFICATION OF OCCURRENCE:
Axial Flux Difference - Outside the Target Band.
This report was initiated by Incident Reports 81-505, 81-506, 81-507, and 81-508.
CONDITIONS PRIOR TO OCCURRENCE:
12-19-81  Mode 1 - Rx Power 50% - Unit Load 580 MWe 12-21-81  Mode 1 - Rx Power 48% - Unit Load 560 MWe DESCRIPTION OF OCCURRENCE:
On four separate occasions, due to Load Rejection Testing, the Axial Flux Difference (AFD) shifted outside the +5% target band.
On December 19, 1981 at 0125, 0623, and 2220 hours, during power reductions of 75% to 50%, 75% to 57%, and 85% to 50%, the AFD d
shifted outside the target band and Action Statement 3.2.1.a.2 was entered. Again, at 2040 hours, December 21, 1981, a power-reduction from 85% to 48% shifted the AFD outside the target.
kand and the Action Statement was entered.
This occurrence constituted operation in a degraded mode in accordance with Technical Specification 6.9.1.9.b.
DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:
As power decreased, the AFD shifted upward. At the same time, the rods going in pushed the flux downward, causing the AFD to shift out of the target band.
ANALYSIS OF OCCURRENCE:
Technical Specification 3.2.1.a.2 requires:
Power operation may continue provided the indicated AFD has not been outside of the +5% target band for more than 1 hour penalty deviation cumulative during the previous 24 hours, and the indicated AFD is within the limits shown on Figure 3.2-1. Otherwise, reduce thermal power within 30 minutes.
 
LER 130/03L CORRECTIVE ACTION:
After the control rods were in and the flux stabilized, the AFD shifted back into the +5% target band. At 0148, 0628, and 2248 hours December 19, 198T, and 2107 hours, December 21, 1981, respectively, Action Statement 3.2.1.a.2 was terminated.
FAILURE DATA:
Not Applicable Prepared By    F. Dickey                    //cI  h[  '"
GendraY Manager -
Salem Operations SORC Meeting No. 82- 08 v}}