ENS 40447: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
Line 16: | Line 16: | ||
| event date = 01/13/2004 13:00 CST | | event date = 01/13/2004 13:00 CST | ||
| last update date = 01/14/2004 | | last update date = 01/14/2004 | ||
| title = 24 Hour Notification | | title = 24 Hour Notification for Bulletin 91-01 Loss of Criticality Safety Controls Involving Waste Drum | ||
| event text = At 1300 on 01/13/04, the Plant Shift Superintendent (PSS) was notified that a waste drum was not characterized and handled properly as fissile waste. During the investigation of ATRC-03-4095, container RFD# 213439-01, which had been characterized as NCS spacing exempt based on the drum being heterogeneous material, it was identified that this waste drum contained solid uranium deposit material violating NCSA WMO-001. The purpose of this NCSA requirement is to determine if the waste drum requires two independent characterization results. Two independent characterization methods were not utilized for the characterization of this drum. | | event text = At 1300 on 01/13/04, the Plant Shift Superintendent (PSS) was notified that a waste drum was not characterized and handled properly as fissile waste. During the investigation of ATRC-03-4095, container RFD# 213439-01, which had been characterized as NCS spacing exempt based on the drum being heterogeneous material, it was identified that this waste drum contained solid uranium deposit material violating NCSA WMO-001. The purpose of this NCSA requirement is to determine if the waste drum requires two independent characterization results. Two independent characterization methods were not utilized for the characterization of this drum. | ||
SAFETY SIGNIFICANCE OF EVENTS: Safety significance of event Is low due to the fact that Nondestructive Assay characterization results of drum contents indicate a total U235 content of less than the safe mass limit for NCS Spacing Exempt waste. | SAFETY SIGNIFICANCE OF EVENTS: Safety significance of event Is low due to the fact that Nondestructive Assay characterization results of drum contents indicate a total U235 content of less than the safe mass limit for NCS Spacing Exempt waste. |
Revision as of 22:24, 1 March 2018
Where | |
---|---|
Paducah Gaseous Diffusion Plant Paducah, Kentucky (NRC Region 2) | |
License number: | Gdp-1 |
Reporting | |
Response | |
Time - Person (Reporting Time:+18.88 h0.787 days <br />0.112 weeks <br />0.0259 months <br />) | |
Opened: | Eric Walker 13:53 Jan 14, 2004 |
NRC Officer: | Jeff Rotton |
Last Updated: | Jan 14, 2004 |
40447 - NRC Website | |