ENS 44238: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 05/24/2008 09:54 EDT
| event date = 05/24/2008 09:54 EDT
| last update date = 05/25/2008
| last update date = 05/25/2008
| title = Loss Of Offsite Power
| title = Loss of Offsite Power
| event text = The licensee entered an Unusual Event after an automatic reactor trip due to a loss of offsite power per EAL Designation PU-1.  Currently the plant is stable in Mode 3 with power being supplied to the "A" & "B" Emergency Diesel Generators (EDG) running supplying power to the safety buses.  Decay heat is being removed by the motor driven Auxiliary Feedwater Pump supplying water to the steam generators exhausting to atmosphere via atmospheric relief valves.  There are no primary to secondary tube leaks.
| event text = The licensee entered an Unusual Event after an automatic reactor trip due to a loss of offsite power per EAL Designation PU-1.  Currently the plant is stable in Mode 3 with power being supplied to the "A" & "B" Emergency Diesel Generators (EDG) running supplying power to the safety buses.  Decay heat is being removed by the motor driven Auxiliary Feedwater Pump supplying water to the steam generators exhausting to atmosphere via atmospheric relief valves.  There are no primary to secondary tube leaks.
NRC Resident Inspector has been notified.
NRC Resident Inspector has been notified.

Latest revision as of 21:14, 1 March 2018

ENS 44238 +/-
Where
Millstone Dominion icon.png
Connecticut (NRC Region 1)
Reporting
Emergency class: Unusual Event
10 CFR 50.72(a) (1) (i), Emergency Class Declaration

10 CFR 50.72(b)(2)(iv)(B), RPS Actuation
Time - Person (Reporting Time:+-3.85 h-0.16 days <br />-0.0229 weeks <br />-0.00527 months <br />)
Opened: Maria Gharakhanian
10:03 May 24, 2008
NRC Officer: Pete Snyder
Last Updated: May 25, 2008
44238 - NRC Website
Loading map...