| title = Unplanned Loss | | title = Unplanned Loss of Shutdown Cooling Due to Containment Isolation | ||
| event text = On Saturday, September 20, 2008, Monticello Nuclear Generating Plant (MNGP) experienced an actuation of the following systems: Reactor Protection System (with the reactor shutdown), Containment Isolation, and Emergency Diesel Generators. | | event text = On Saturday, September 20, 2008, Monticello Nuclear Generating Plant (MNGP) experienced an actuation of the following systems: Reactor Protection System (with the reactor shutdown), Containment Isolation, and Emergency Diesel Generators. | ||
The apparent cause of the actuation was a pressure pulse in the reference leg of a Reactor level instrument that resulted when a CRD [Control Rod Drive] pump was started without the reference leg backfill system isolated from the CRD system. | The apparent cause of the actuation was a pressure pulse in the reference leg of a Reactor level instrument that resulted when a CRD [Control Rod Drive] pump was started without the reference leg backfill system isolated from the CRD system. |
Latest revision as of 22:13, 1 March 2018
Where | |
---|---|
Monticello Minnesota (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
Time - Person (Reporting Time:+-0.37 h-0.0154 days <br />-0.0022 weeks <br />-5.06826e-4 months <br />) | |
Opened: | Matt Schillerstrom 02:13 Sep 21, 2008 |
NRC Officer: | Howie Crouch |
Last Updated: | Sep 21, 2008 |
44508 - NRC Website
| |