Line 16: Line 16:
| event date = 09/20/2008 21:35 CDT
| event date = 09/20/2008 21:35 CDT
| last update date = 09/21/2008
| last update date = 09/21/2008
| title = Unplanned Loss Of Shutdown Cooling Due To Containment Isolation
| title = Unplanned Loss of Shutdown Cooling Due to Containment Isolation
| event text = On Saturday, September 20, 2008, Monticello Nuclear Generating Plant (MNGP) experienced an actuation of the following systems:  Reactor Protection System (with the reactor shutdown), Containment Isolation, and Emergency Diesel Generators.   
| event text = On Saturday, September 20, 2008, Monticello Nuclear Generating Plant (MNGP) experienced an actuation of the following systems:  Reactor Protection System (with the reactor shutdown), Containment Isolation, and Emergency Diesel Generators.   
The apparent cause of the actuation was a pressure pulse in the reference leg of a Reactor level instrument that resulted when a CRD [Control Rod Drive] pump was started without the reference leg backfill system isolated from the CRD system.  
The apparent cause of the actuation was a pressure pulse in the reference leg of a Reactor level instrument that resulted when a CRD [Control Rod Drive] pump was started without the reference leg backfill system isolated from the CRD system.  

Latest revision as of 22:13, 1 March 2018

ENS 44508 +/-
Where
Monticello Xcel Energy icon.png
Minnesota (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(iv)(A), System Actuation
Time - Person (Reporting Time:+-0.37 h-0.0154 days <br />-0.0022 weeks <br />-5.06826e-4 months <br />)
Opened: Matt Schillerstrom
02:13 Sep 21, 2008
NRC Officer: Howie Crouch
Last Updated: Sep 21, 2008
44508 - NRC Website