Line 16: | Line 16: | ||
| event date = 02/12/2014 08:15 CST | | event date = 02/12/2014 08:15 CST | ||
| last update date = 02/12/2014 | | last update date = 02/12/2014 | ||
| title = Service Water Radiation Monitor Removed | | title = Service Water Radiation Monitor Removed from Service for Planned Maintenance | ||
| event text = Planned preventive maintenance on service water piping will remove the service water radiation monitor from service. As a result, this represents a loss of emergency assessment capability under NUREG 1022, Revision 3, since the radiation monitor is used to assess NUE [Notification of Unusual Event] and Alert thresholds. The planned maintenance is expected to last 8 hours. During this time, the site Chemistry Department will perform sampling at this location every 30 minutes. The sampling is documented in a station procedure and allows the ability to detect NUE levels in a timely manner. As a result of sampling, reasonable assurance exists to monitor and detect rising radiation levels in order to protect the health and safety of the public. | | event text = Planned preventive maintenance on service water piping will remove the service water radiation monitor from service. As a result, this represents a loss of emergency assessment capability under NUREG 1022, Revision 3, since the radiation monitor is used to assess NUE [Notification of Unusual Event] and Alert thresholds. The planned maintenance is expected to last 8 hours. During this time, the site Chemistry Department will perform sampling at this location every 30 minutes. The sampling is documented in a station procedure and allows the ability to detect NUE levels in a timely manner. As a result of sampling, reasonable assurance exists to monitor and detect rising radiation levels in order to protect the health and safety of the public. | ||
The NRC Resident Inspector will be notified prior to removing the service water radiation monitor from service. | The NRC Resident Inspector will be notified prior to removing the service water radiation monitor from service. |
Latest revision as of 20:51, 1 March 2018
Where | |
---|---|
Monticello Minnesota (NRC Region 3) | |
Reporting | |
10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
Time - Person (Reporting Time:+-4.8 h-0.2 days <br />-0.0286 weeks <br />-0.00658 months <br />) | |
Opened: | Randy Sand 09:27 Feb 12, 2014 |
NRC Officer: | Daniel Mills |
Last Updated: | Feb 12, 2014 |
49820 - NRC Website
| |